Permit Information
Permit NumberELE10-01478
StatusFinaled
Name S K ELECTRIC
Site Address 171 S COSTON LN
Project Name 
Customer Number 
ePlanReview 
Description
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final7/9/20107/9/20107/9/2010APASS
DetailsBob Reichert
Bob the trench is deeper and we have wired the irrigation pump. Any questions please give me a call ###-#### Thanks Shaun Inspection requested from web by: Shaun Kirkman Phone #: ###-#### ok cover u/g. ok to final
Electrical Rough-In7/7/20107/7/20107/7/2010PCANC
DetailsBob Reichert
trench has been dug deeper for conduit Inspection requested from web by: Shaun Kirkman Phone #: ###-#### contractor called and wants to reschedule after pump installed
Rough-In Permanent Service7/2/20107/2/20107/2/2010PCANC
DetailsBob Reichert
richard Phone #: ###-#### see ri and p/s
Electrical Rough-In7/2/20107/2/20107/2/2010PFAIL
DetailsBob Reichert
richard Phone #: ###-#### called gave correction notice, NEC 300.5 u/g for pvc shall be 18" deep, not 12"
Electrical Rough-In7/2/20107/2/20107/2/2010PFAIL
DetailsBob Reichert
richard Phone #: ###-#### called gave correction notice, NEC 300.5 u/g for pvc shall be 18" deep, not 12"
Permanent Service7/2/20107/2/20107/2/2010PPASS
DetailsBob Reichert
richard Phone #: ###-#### p/s o/h n ok