Information based on query as of Tuesday, July 16, 2024.
Permit Information
Permit NumberELE10-02675
StatusFinaled
Name ALLSOURCE ELECTRIC
Site Address 1955 S DOE CREEK WAY
Project Name 
Customer Number 
ePlanReviewNo
Description
adding circuits in the basement
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final2/3/20112/4/20112/4/2011APASS
DetailsJack Frank
Final inspection for basement remodle. home owner, Shanda Palsulich #208.484.3823 >> Inspection requested via web by Billy Ellison
Electrical Rough-In12/9/201012/9/201012/9/2010PPASS
DetailsJack Frank
billy - late afternoon please Phone #: ###-####
Electrical Rough-In12/8/201012/8/201012/8/2010PFAIL
DetailsBob Reichert
Billy or ###-#### Shanda Phone #: ###-#### called, left correction notice, BCC shall provide at least 6 rooms on permit, all make-up shall be done, NEC 300.14 shall provide 6" free conductor length at all boxes, 210.52 shall provide receptacle in 2' wall space, 334.30 shall secure cable within 12" of panel, 300.4(A)&(D) edge of bored holes and nm cable shall be 1 1/4" from edge of framing members, Note: corrections shall be made within 5 working days