Information based on query as of Wednesday, July 17, 2024.
Permit Information
Permit NumberELE11-01335
StatusFinaled
Name ULTIMATE ELECTRIC LLC
Site Address 3855 N MAPLE GROVE RD
Project Name 
Customer Number 
ePlanReviewNo
Description
Electrical Permit - New: New construction house
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final8/5/20118/8/20118/8/2011APASS
DetailsDaryl DeGrange
Key inside front w/p receptacle box for access Phone #: ###-#### >> Inspection requested via web by daniel bibikov final ok
Final8/5/20118/5/20118/5/2011PFAIL
DetailsDaryl DeGrange
Phone #: ###-#### >> Inspection requested via web by daniel bibikov 110.12 Mechanical execution of work Main bath two gang box, Several extra holes drilled in two locations for fishing additional nm cable into switch box do to incomplete circuitry. The outer NM cable sheath shall extend at least 1/4 inch inside device enclosure
Final8/4/20118/5/20118/5/2011AFAIL
DetailsDoug A Poedy
Phone #: ###-#### >> Inspection requested via web by daniel bibikov. NEC 210.8 Garage door opener must be on GFCI. NEC 110.3 South hallway switch not working.
Permanent Service8/1/20118/1/20118/1/2011PPASS
DetailsDoug A Poedy
Phone #: ###-#### >> Inspection requested via web by daniel bibikov. P/S Connect ok.
Rough-In Permanent Service6/23/20116/23/20116/23/2011PPASS
DetailsDaryl DeGrange
Phone #: ###-#### >> Inspection requested via web by daniel bibikov rough-in ok but no permanent service- overhead service mask needs to be at least 2 in IMC if going to be point of attachment.