Permit Information
Permit NumberELE11-02545
StatusFinaled
Name CORNERSTONE ELECTRIC
Site Address 2521 W PALOUSE ST
Project Name 
Customer Number 
ePlanReviewNo
Description
Electrical Permit - Alteration: Powerto detached building
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final2/29/20123/1/20123/1/2012PPASS
DetailsDoug A Poedy
Cal Phone #: ###-#### >> Inspection requested via web by cal crosby
Final2/24/20122/24/20122/24/2012PFAIL
DetailsDaryl DeGrange
Cal Phone #: ###-#### NEC 250.24 The grounded conductor (neutral) from an 4 wire branch circuit shall orginate from the grounding bar along with the equipment grounding conductor. NEC250.32(A) Buildings supplied by feeders or branch circuits shall have a grounding eletrode.NEC 250.56 A single electode consisting of a rod pipe, or plate that does not have a resistance of 25 ohms or less shall be argmented by an additional electrode NEC 300.4 Shall provide nail plates were NM cable or bored holes are less than 1 1/4 from edge of framing member
Conference11/9/201111/9/201111/9/2011PCANC
DetailsBob Reichert
I need a trinch inspection only Please
Trinch is in back call for any Questions Phone #: ###-#### >> Inspection requested via web by cal crosby see ri
Electrical Rough-In11/9/201111/9/201111/9/2011PPASS
DetailsBob Reichert
ok cover u/g only