Permit NumberELE11-02554
StatusFinaled
Name PREHN DONNELLY L
Site Address 2503 S VIRGINIA ST
Project Name 
Customer Number 
ePlanReviewNo
Description
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final6/22/20126/22/20126/22/2012PPASS
DetailsBob Reichert
Please call prior for access -- Don Phone #: ###-#### ok final
Final4/3/20124/4/20124/4/2012AFAIL
DetailsBob Reichert
don please call for access Phone #: ###-#### met owner, shall provide tamper proof receptacles, tighten loose receptacle, id breakers, outdoor receptacle shall be weather resistant
Electrical Rough-In12/14/201112/14/201112/14/2011PPASS
DetailsBob Reichert
corrections made, ri ok
Electrical Rough-In12/12/201112/13/201112/13/2011ANR
DetailsBob Reichert
don Phone #: ###-#### met owner, reviewed correction notice, will fix and recall
Electrical Rough-In12/12/201112/12/201112/12/2011PFAIL
DetailsBob Reichert
Please call 20min prior for access---Don Phone #: ###-#### corrections not made
Electrical Rough-In12/8/201112/9/201112/9/2011PFAIL
DetailsBob Reichert
don please call before going out- Phone #: ###-#### called, left correction notice, NEC 300.14 shall provide 6" free conductor at box, 250.86 shall provide ground screw in metal boxes, 300.4(A)(D) edge of bored holes and nm cable shall be 1 1/4" from edge of framing member, 314.16 shall not exceed box fill, 334.30 shall staple nm within 12" of box or314.17(C) shall staple nm within 8" if more than 1 nm enters box, BCC all make-up shall be done
Conference11/14/201111/14/201111/14/2011PDONE
DetailsBob Reichert
Please call 20min prior for access---Don Phone #: ###-#### talked about room addition wiring, when to call for ri, owner only doing wiring