Final | 3/15/2012 | 3/15/2012 | 3/15/2012 | P | PASS |
Daryl DeGrange
|
|
|
Phone #: ###-#### >> Inspection requested via web by TRAVIS WARFIELD final ok
|
Final | 3/12/2012 | 3/14/2012 | 3/14/2012 | P | FAIL |
Daryl DeGrange
|
|
|
Phone #: ###-#### >> Inspection requested via web by TRAVIS WARFIELD NEC 410.16 Does not meet minmun clearance distance 12in for surface-mounted incandescent. Basement bedroom closet luminaire
|
Permanent Service | 12/23/2011 | 12/23/2011 | 12/23/2011 | A | PASS |
Daryl DeGrange
|
|
|
p/s o/h rec ok
|
Electrical Rough-In | 12/22/2011 | 12/23/2011 | 12/23/2011 | A | PASS |
Daryl DeGrange
|
|
|
all so need the service inspected Phone #: ###-#### >> Inspection requested via web by TRAVIS WARFIELD rough-in ok cover
|
Electrical Rough-In | 12/21/2011 | 12/22/2011 | 12/22/2011 | A | FAIL |
Daryl DeGrange
|
|
|