Permit Information
Permit NumberELE11-02819
StatusFinaled
Name BROTHERS ELECTRIC
Site Address 1918 W RIDENBAUGH ST
Project Name 
Customer Number340 2173
ePlanReviewNo
Description
Electrical Permit - New
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final3/15/20123/15/20123/15/2012PPASS
DetailsDaryl DeGrange
Phone #: ###-#### >> Inspection requested via web by TRAVIS WARFIELD final ok
Final3/12/20123/14/20123/14/2012PFAIL
DetailsDaryl DeGrange
Phone #: ###-#### >> Inspection requested via web by TRAVIS WARFIELD NEC 410.16 Does not meet minmun clearance distance 12in for surface-mounted incandescent. Basement bedroom closet luminaire
Permanent Service12/23/201112/23/201112/23/2011APASS
DetailsDaryl DeGrange
p/s o/h rec ok
Electrical Rough-In12/22/201112/23/201112/23/2011APASS
DetailsDaryl DeGrange
all so need the service inspected Phone #: ###-#### >> Inspection requested via web by TRAVIS WARFIELD rough-in ok cover
Electrical Rough-In12/21/201112/22/201112/22/2011AFAIL
DetailsDaryl DeGrange
Phone #: ###-#### >> Inspection requested via web by TRAVIS WARFIELD NEC 300.4(A) Edge of bored holes and NM cable shall be at least 1 1/4 from edge of framing member. NEC 334.30 Shall staple NM cable within 12 inches of box NEC 210.52 (2) small appliance branch circuit shall have no other outlets