ELE-Aging Inspection | 10/2/2014 | 10/2/2014 | 10/2/2014 | | DONE |
Rock A. Hudson
|
|
|
Completed at phase 3 inspection
|
Final | 10/2/2014 | 10/2/2014 | 10/2/2014 | P | PASS |
Rock A. Hudson
|
|
|
Final ok
|
Final | 6/27/2014 | 7/1/2014 | 6/30/2014 | A | CANC |
Rock A. Hudson
|
|
|
We are requesting a Fire Alarm inspection for Tuesday July 1st in the am. Our onsite contact is Bryant Adams @ ###-####. Thanks. Phone #: ###-#### >> Inspection requested via web by Clint Tate Electrical does not inspect final for fire
|
Final | 6/27/2014 | 6/30/2014 | 6/30/2014 | A | PART |
Rock A. Hudson
|
|
|
We are requesting a final electrical inspection for Monday, June 30th in the am. Our onsite contact is Bryant Adams @ ###-####. Thank you. Phone #: ###-#### >> Inspection requested via web by Clint Tate Phase 3 ER remodel final ok
|
Final | 6/27/2014 | 6/30/2014 | 6/27/2014 | A | CANC |
Rock A. Hudson
|
|
|
We are requesting a final inspection for Monday June 30th in the am. Our onsite contact is Bryant Adams @ ###-####. Thank you. Phone #: ###-#### >> Inspection requested via web by Clint Tate Inspection cancelled from web by: Clint Tate
|
Electrical Rough-In | 6/23/2014 | 6/23/2014 | 6/23/2014 | P | PASS |
Rock A. Hudson
|
|
|
ER phase 3 ceiling grid rough in ok cover
|
Rough-In Permanent Service | 6/20/2014 | 6/23/2014 | 6/23/2014 | A | PART |
Rock A. Hudson
|
|
|
We are requesting a ceiling inspection for the morning of Monday, June 23rd. Our onsite contact is Bryant Adams @ ###-####. Thank you. Phone #: ###-#### >> Inspection requested via web by Clint Tate No service needed Exits siezmic, mini cans in circle, open junctions, couple offices with wires shot not connected to fixures. Borders only ok cover
|
Electrical Rough-In | 6/20/2014 | 6/23/2014 | 6/20/2014 | P | CANC |
Rock A. Hudson
|
|
|
We are requesting a Ceiling inspection for Monday, June 23rd in the afternoon. Our onsite contact is Bryant Adams ###-####. Thank you. Phone #: ###-#### >> Inspection requested via web by Clint Tate Inspection cancelled from web by: Clint Tate
|
Conference | 6/18/2014 | 6/18/2014 | 6/18/2014 | P | DONE |
Rock A. Hudson
|
|
|
We are requesting an electrical consult for today June 18th in the aftermoon. Our onsite contact is Bryant Adams @ ###-####. Thank you. Phone #: ###-#### >> Inspection requested via web by Clint Tate Discussed direct burial depth under ambulance cover, due to vehicle access 24" minimum cover required but due to solid concrete bases note 5 to 300.5 states shallower depth acceptable if encased in min of 2" concrete.
|
Final | 5/14/2014 | 5/15/2014 | 5/15/2014 | A | PART |
Rock A. Hudson
|
|
|
We are requesting a final inspection for the ED Trauma & Resuscitation area. (Please do not close this permit -project is on-going) For tomorrow 5/15/14 in the AM our onsite contact is Bud @ ###-####. Thank you. Phone #: ###-#### >> Inspection requested via web by Clint Tate Area specified final ok
|
Electrical Rough-In | 5/7/2014 | 5/8/2014 | 5/8/2014 | A | PART |
Rock A. Hudson
|
|
|
We are requesting a partial ceiling inspection for tomorrow 5/8/14 during the AM. Our onsite contact is Bud @ ###-####. Thank you. Phone #: ###-#### >> Inspection requested via web by Clint Tate Corridor grid by east trauma rooms rough in ok cover
|
Electrical Rough-In | 4/24/2014 | 4/25/2014 | 4/25/2014 | A | PASS |
Rock A. Hudson
|
|
|
We are requesting a wall rough-in inspection for tomorrow 4/25/14 in the AM. Our onsite contact is Bud Horsley @ ###-####. Thank you. Phone #: ###-#### >> Inspection requested via web by Clint Tate Physicians lounge, corridor, baths, family counselling, utility linen wall rough in ok cover
|
Electrical Rough-In | 4/10/2014 | 4/11/2014 | 4/11/2014 | P | PASS |
Rock A. Hudson
|
|
|
We are requesting a wall rough in inspection for tomorrow 4/11/14 in the afternoon. Our onsite contact is Bud @ ###-####. Thank you. Phone #: ###-#### >> Inspection requested via web by Clint Tate Phase 3 ER panel wall, bathroom walls and lids, Med room, rescorce room Desk area, Nurse desk, and soiled and clean lennon rooms wall and bath lids rough in ok cover
|
Electrical Rough-In | 4/1/2014 | 4/2/2014 | 4/2/2014 | A | PASS |
Rock A. Hudson
|
|
|
We are requesting a partial wall rough-in inspection for tomorrow 4/2/14 in the AM. Our onsite contact is Bud @ ###-####. Thank you. Phone #: ###-#### >> Inspection requested via web by Clint Tate Phase 3 all exam rooms wall rough in ok cover
|
Conference | 4/1/2014 | 4/1/2014 | 4/1/2014 | P | DONE |
Rock A. Hudson
|
|
|
We are requesting a electrical consultation with a city of inspector for today about the sheet rock in front of the exam rooms. Our onsite contact is Bud ###-####. Thank you. Phone #: ###-#### >> Inspection requested via web by Clint Tate Discussed covering upper wall by exam rooms for cable tray installation. Cover ok
|
Electrical Rough-In | 3/19/2014 | 3/20/2014 | 3/20/2014 | A | PASS |
Rock A. Hudson
|
|
|
We are requesting a wall rough-in inspection for tomorrow 3/20/14 in the AM for Trauma/ Resuscitation. Our onsite contact is Bud ###-####. This is an on-going project please leave this permit open. Thank you. Phone #: ###-#### >> Inspection requested via web by Clint Tate Wall rough in ok cover
|
Final | 2/18/2014 | 2/19/2014 | 2/19/2014 | A | CANC |
Daryl DeGrange
|
|
|
bud on site contact (This permit received a final by mistake this is an on going permit.) Phone #: ###-#### should of been scheduled as rough-in
|
Electrical Rough-In | 2/19/2014 | 2/19/2014 | 2/19/2014 | A | PASS |
Daryl DeGrange
|
|
|
bud on site contact (This permit received a final by mistake this is an on going permit.) Phone #: ###-#### Rough-in ok cover underground phase 3 nurses call
|
Final | 1/30/2014 | 2/3/2014 | 2/3/2014 | A | PASS |
Daryl DeGrange
|
|
|
We are requesting Final Inspection for CCD 016 Soiled Linen SARMC for Monday Feb. 3rd in the AM. Our onsite contact is Bud Horsely 208.369.7770. Thank you. Phone #: ###-#### >> Inspection requested via web by Clint Tate job complete, final ok
|
Electrical Rough-In | 1/14/2014 | 1/15/2014 | 1/15/2014 | A | PASS |
Daryl DeGrange
|
|
|
Bud needs a rough-in inspection for CCD-016 soiled linen at SARMC. Bud can be reached at ###-####. Thank you. Phone #: ###-#### >> Inspection requested via web by Clint Tate rough-in ok cover walls and hard lid
|
Permanent Service | 12/23/2013 | 12/24/2013 | 12/24/2013 | A | CANC |
Daryl DeGrange
|
|
|
Bud on site. Final for Phase 2B and staff lounge. Phone #: ###-#### >> Inspection requested via web by Clint Tate
|
Final | 12/24/2013 | 12/24/2013 | 12/24/2013 | P | PART |
Daryl DeGrange
|
|
|
Bud on site. Final for Phase 2B and staff lounge. Phone #: ###-#### >> Inspection requested via web by Clint Tate partial final ok
|
Electrical Rough-In | 12/17/2013 | 12/18/2013 | 12/18/2013 | P | PASS |
Daryl DeGrange
|
|
|
Requesting ceiling inspection for 12/18/13 afternoon. Please contact Bud Horsley with any questions. Phone #: ###-#### >> Inspection requested via web by Clint Tate rough-in ok cover ceiling grid SAR phase 2B
|
Electrical Rough-In | 12/10/2013 | 12/12/2013 | 12/12/2013 | A | PASS |
Daryl DeGrange
|
|
|
Bud on site. Ceiling inspection. Staff lounge. Phone #: ###-#### >> Inspection requested via web by Clint Tate rough-in ok cover
|
Final | 11/26/2013 | 11/27/2013 | 11/27/2013 | A | PART |
Daryl DeGrange
|
|
|
Bud on site. Request partial final for CCD-011 - temporary exam rooms. Phone #: ###-#### >> Inspection requested via web by Clint Tate partial final ok
|
Rough-In Permanent Service | 11/8/2013 | 11/12/2013 | 11/12/2013 | A | CANC |
Daryl DeGrange
|
|
|
A ceiling inspection for the CCD number 011 is being requested. Please contact Bud Horsely with any questions. Phone #: ###-#### >> Inspection requested via web by Clint Tate
|
Electrical Rough-In | 11/12/2013 | 11/12/2013 | 11/12/2013 | P | PASS |
Daryl DeGrange
|
|
|
A ceiling inspection for the CCD number 011 is being requested. Please contact Bud Horsely with any questions. Phone #: ###-#### >> Inspection requested via web by Clint Tate rough-in ok cover ceiling grid
|
Electrical Rough-In | 11/8/2013 | 11/12/2013 | 11/12/2013 | A | PASS |
Daryl DeGrange
|
|
|
A wall inspection for the 2B phase of this project is being requested. Please contact Bud Horsely with any questions. Phone #: ###-#### >> Inspection requested via web by Clint Tate rough-in ok cover
|
Electrical Rough-In | 11/1/2013 | 11/4/2013 | 11/4/2013 | A | PASS |
Daryl DeGrange
|
|
|
Bud on site. Wall rough-in for Phase 2B South Phone #: ###-#### >> Inspection requested via web by Clint Tate rough-in ok cover walls
|
Electrical Rough-In | 10/22/2013 | 10/23/2013 | 10/23/2013 | A | PASS |
Daryl DeGrange
|
|
|
Bud on site. Wall rough-in. Phone #: ###-#### >> Inspection requested via web by Clint Tate Rough-in ok cover east and south walls in phase 2
|
Electrical Rough-In | 10/8/2013 | 10/9/2013 | 10/9/2013 | A | PASS |
Daryl DeGrange
|
|
|
Rough in for the Temp Exam Rooms. Bud Horsely is the contact. Phone #: ###-#### >> Inspection requested via web by Clint Tate rough-ok cover
|
Final | 9/19/2013 | 9/20/2013 | 9/20/2013 | A | PART |
Daryl DeGrange
|
|
|
Bud on site. Do not close permit. This is a final for the x-ray and phase 2A only. Phone #: ###-#### >> Inspection requested via web by Clint Tate Partial final ok UL listed X-ray equipment
|
Final | 9/12/2013 | 9/13/2013 | 9/13/2013 | A | PART |
Daryl DeGrange
|
|
|
Bud on site. Final for Phase 2A. Phone #: ###-#### >> Inspection requested via web by Clint Tate partial final ok
|
Electrical Rough-In | 8/29/2013 | 8/29/2013 | 8/29/2013 | A | PASS |
Daryl DeGrange
|
|
|
rough-in ok cover ceiling grid phase 2A
|
Final | 8/28/2013 | 8/29/2013 | 8/29/2013 | A | NR |
Daryl DeGrange
|
|
|
Ceiling final for phase 2A. Phone #: ###-#### >> Inspection requested via web by Clint Tate Not ready for final at this time.
|
Electrical Rough-In | 7/24/2013 | 7/24/2013 | 7/24/2013 | A | PASS |
Daryl DeGrange
|
|
|
underground for three ballards at front entry drive rough-in ok cover
|
Conference | 7/23/2013 | 7/24/2013 | 7/24/2013 | A | PASS |
Daryl DeGrange
|
|
|
Sheet rocking one side of walls in temp exam room. Phone #: ###-#### >> Inspection requested via web by Clint Tate Ok cover one side Over Flow room, exterior walls
|
Electrical Rough-In | 7/3/2013 | 7/8/2013 | 7/8/2013 | A | PASS |
Daryl DeGrange
|
|
|
Phone #: ###-#### >> Inspection requested via web by Clint Tate rough-in ok cover front entry lobby as per highlighted and dated on plans
|
Electrical Rough-In | 6/27/2013 | 6/28/2013 | 6/28/2013 | A | PASS |
Daryl DeGrange
|
|
|
Partial wall rough-in for phase 2A, Emergency Room remodel. Phone #: ###-#### >> Inspection requested via web by Clint Tate rough-ok cover area highlighted and dated
|
Electrical Rough-In | 6/20/2013 | 6/21/2013 | 6/21/2013 | A | PASS |
Daryl DeGrange
|
|
|
Wall rough in for exam rooms in phase 2A Phone #: ###-#### >> Inspection requested via web by Clint Tate rough-in ok cover as highlighted and dated on plans
|
Conference | 6/5/2013 | 6/6/2013 | 6/6/2013 | A | DONE |
Daryl DeGrange
|
|
|
Bud on site. Conference to discuss sheet rocking one side of exam room walls. Phone #: ###-#### >> Inspection requested via web by Clint Tate Discussed need to hang sheet to install cable trays, one side ok only in areas of cable tray.
|
Final | 3/4/2013 | 3/5/2013 | 3/6/2013 | A | PART |
Daryl DeGrange
|
|
|
Please keep permit open. This is a final for phase 1 only. Phone #: ###-#### >> Inspection requested via web by Clint Tate Partial final Phase One ok
|
Electrical Rough-In | 2/22/2013 | 2/25/2013 | 2/25/2013 | A | PASS |
Bob Reichert
|
|
|
Bud on site. Ceiling inspection. Phone #: ###-#### >> Inspection requested via web by Clint Tate ok cover phase 1 ceiling only anop
|
Electrical Rough-In | 1/23/2013 | 1/25/2013 | 1/25/2013 | A | PASS |
Daryl DeGrange
|
|
|
Rough in wall inspection. Phone #: ###-#### >> Inspection requested via web by Clint Tate rough-in ok cover walls exam rooms as highlighted and dated on plans
|
Electrical Rough-In | 1/8/2013 | 1/9/2013 | 1/9/2013 | A | PASS |
Daryl DeGrange
|
|
|
Bud on site. Phone #: ###-#### >> Inspection requested via web by Clint Tate rough-in ok cover walls as per highlighted and dated on plans
|
Conference | 11/6/2012 | 11/7/2012 | 11/7/2012 | A | DONE |
Daryl DeGrange
|
|
|
Phone #: ###-#### >> Inspection requested via web by Clint Tate NEC 110.26(F)(1)(a) Dedicated Electrical Space The space equal to thr width and depth of the equipment and extending from the floor to a height of 6ft. above the equipment to the structural ceiling shall be dedicated to the elecetrical installation. No piping,ducts,leak protection apparatus or other equipment foreign to the electrical installation shall be located in this zone. Shall relocate duct, provide drip gutter over non-access area of Critical operation power system equipment
|