Final | 2/27/2014 | 2/28/2014 | 2/28/2014 | A | PASS |
Rex Boyles
|
|
|
Correction have been made. Please call Bill ahead for entry. Phone #: ###-#### >> Inspection requested via web by Rhonda Yoast final ok
|
Final | 2/20/2014 | 2/21/2014 | 2/21/2014 | A | FAIL |
Rock A. Hudson
|
|
|
Please call Bill ahead for entry. Phone #: ###-#### >> Inspection requested via web by Rhonda Yoast 314.20 Outside lights, if boxes are recessed more than 1/4" plaster ring shall be installed. 314.23 non mettalic boxes shall be securily mounted (oven). 230.77-service disconnect shall be legibly identified.
|
Rough-In Permanent Service | 9/11/2013 | 9/12/2013 | 9/12/2013 | A | PASS |
Daryl DeGrange
|
|
|
This is a reinspection Phone #: ###-#### >> Inspection requested via web by Rhonda Yoast Corrections done rough-in p/s u/g n ok main house and detach garage
|
Rough-In Permanent Service | 9/9/2013 | 9/10/2013 | 9/10/2013 | A | FAIL |
Rock A. Hudson
|
|
|
Phone #: ###-#### >> Inspection requested via web by Rhonda Yoast 300.4 NM cable shall be protected from physical damage up front bed, up back bed, entry and office and pantry. 250 Metal piping system shall be bonded if 10' or more continuous copper.
|
Electrical Rough-In | 6/12/2013 | 6/12/2013 | 6/12/2013 | P | PASS |
Bob Reichert
|
|
|
Please inspect trench in ground. If you have any questions call Bill @ ###-####. Phone #: ###-#### >> Inspection requested via web by Rhonda Yoast u/g house to garage ok cover
|