Final | 12/10/2013 | 12/11/2013 | 12/11/2013 | A | PASS |
Rock A. Hudson
|
|
|
Garage code is 6767 Phone #: ###-#### >> Inspection requested via web by TOM BICANDI Final ok
|
Final | 10/18/2013 | 10/18/2013 | 10/18/2013 | P | FAIL |
Rock A. Hudson
|
|
|
Garage code is 6767, also key is in front outlet. Phone #: ###-#### >> Inspection requested via web by TOM BICANDI 406.5- Receptical face plates shall be installed. Garage 210.8- Receptical located with in 6' of sink shall have GFCI protection. 210.52- 2' wall space in bed shall have receptical outlet installed. 314.16- Boxes shall be of sufficient size to provide space for all conductors. Island.
|
Rough-In Permanent Service | 6/28/2013 | 7/1/2013 | 7/1/2013 | A | PASS |
Rock A. Hudson
|
|
|
Phone #: ###-#### >> Inspection requested via web by TOM BICANDI Rough in ok cover p/s u/g n ok
|
Final | 6/28/2013 | 7/1/2013 | 6/28/2013 | A | CANC |
Rock A. Hudson
|
|
|
Phone #: ###-#### >> Inspection requested via web by TOM BICANDI Inspection cancelled from web by: TOM BICANDI
|
Rough-In Permanent Service | 6/28/2013 | 6/28/2013 | 6/28/2013 | A | FAIL |
Rock A. Hudson
|
|
|
Phone #: ###-#### >> Inspection requested via web by TOM BICANDI 300.4- NM cable shall be secured at least 1 1/4" from surface of framing member. 334.30 NM cable shall be secured with in 12" of bath fan j-box. 314.4- Metal boxes shall be grounded and bonded. 250.112- non current carrying metal parts shall be grounded.
|