Permit Information
Permit NumberELE13-01989
StatusFinaled
Name PRIORITY ELECTRIC
Site Address 2750 S PALMATIER WAY
Project Name 
Customer Number585-3477
ePlanReviewNo
Description
Electrical Permit - New: New ground up community center for harris ranch subdivision. Community center only all other work for pool and pumps done by others. 400 Amp service single phase.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final12/11/201312/12/201312/12/2013APASS
DetailsBob Reichert
Phone #: ###-#### >> Inspection requested via web by Thomas Jenkins corrections made, ok final, no card found to sign
Final12/9/201312/10/201312/10/2013AFAIL
DetailsBob Reichert
Phone #: ###-#### >> Inspection requested via web by Thomas Jenkins called, left correction notice, NEC 110.26(A) shall provide work space for transformer, 400.8 shall not use flexible cord or cable as a substitute for fixed wiring
Final11/21/201311/21/201311/21/2013PPART
DetailsBob Reichert
partial final for occupancy. Phone #: ###-#### >> Inspection requested via web by Thomas Jenkins corrections made, t/o ok, will sign card at final, after all pool equipment installed
Final11/20/201311/20/201311/21/2013PFAIL
DetailsBob Reichert
Phone #: ###-#### >> Inspection requested via web by Thomas Jenkins called, outdoor receptacles shall be wr type per NEC 406.8, shall close openings in box in wall, at final, need to part final until all pool equipment installed
Permanent Service11/12/201311/13/201311/13/2013APASS
DetailsBob Reichert
Phone #: ###-#### >> Inspection requested via web by Thomas Jenkins corrections made, p/s u/g n ok
Permanent Service11/12/201311/12/201311/12/2013PFAIL
DetailsRock A. Hudson
tom Phone #: ###-#### 250.24- Grounding electrode conductor shall terminate at the same busbar or terminal as grounded conductor.
310.15(B)- 400 amp service shall be fed with parallel 3/0 or equivalent single condutors. 310.15(C)- Provide calculation to prove wingle conductor 3/0 conductors adequate.
Electrical Rough-In11/5/201311/5/201311/5/2013PPASS
DetailsRock A. Hudson
Phone #: ###-#### >> Inspection requested via web by Thomas Jenkins Locker and bath rooms ceiling rough in ok cover
Final11/5/201311/5/201311/5/2013PPASS
DetailsRock A. Hudson
Phone #: ###-#### >> Inspection requested via web by Thomas Jenkins Service final ok
Electrical Rough-In10/16/201310/16/201310/16/2013PPASS
DetailsBob Reichert
Walls in post office Phone #: ###-#### >> Inspection requested via web by Thomas Jenkins ok cover post office walls, ceiling
Electrical Rough-In8/28/20138/28/20138/28/2013PPASS
DetailsDaryl DeGrange
Ruffin of boxes in concrete walls Phone #: ###-#### >> Inspection requested via web by Thomas Jenkins rough-in ok cover
Electrical Rough-In8/27/20138/28/20138/28/2013ANR
DetailsBob Reichert
rough in of masonry boxes in concrete walls. Phone #: ###-#### >> Inspection requested via web by Thomas Jenkins called, left message
Electrical Rough-In7/29/20137/29/20137/29/2013PPASS
DetailsBob Reichert
Inspection for uffer. Phone #: ###-#### >> Inspection requested via web by Thomas Jenkins ok pour concrete encased electrode