Permit Information
Permit NumberELE13-02793
StatusFinaled
Name RUMMER ELECTRIC
Site Address 106 N CASTELLO PL
Project Name 
Customer Number34550
ePlanReviewNo
Description
Electrical Permit - New: new // running conduit for pool (actual pool being done by other contractor) and added 1 room for tennis court lights per call from Rummer Electric 10/29/13 leg
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final2/17/20142/18/20142/18/2014APASS
DetailsRock A. Hudson
garage code 8898 Phone #: ###-#### >> Inspection requested via web by Neal Rumsey final ok corrections made
Final2/13/20142/14/20142/14/2014AFAIL
DetailsBob Reichert
garage code 88989 Phone #: ###-#### >> Inspection requested via web by Neal Rumsey called, left correction notice, NEC 210.52(B) pantry shall have gfci receptacles, 210.52(A)(2) mbr wall space over 2' shall have receptacles, 250.94 shall provide intersystem bond bar, 352.30 shall strap pvc within 3' of termination, NOTE: basement room has no receptacles, provide switch cover screws
Electrical Rough-In10/29/201310/29/201310/29/2013PPASS
DetailsRock A. Hudson
Tennis light, pool equipment Phone #: ###-#### >> Inspection requested via web by Neal Rumsey Pending pull point at end of lower wall. Rough in ok cover
Final10/22/201310/23/201310/23/2013AFAIL
DetailsBob Reichert
Ran conduit for pool and tennis light Phone #: ###-#### >> Inspection requested via web by Neal Rumsey called, shall include pool and tennis court on permit, NEC 300.5 shall bury conduit correct depth, 352.26 shall not be over 360 degree bend in raceway, 300.11 shall not use raceway as means of support
Rough-In Permanent Service10/10/201310/10/201310/10/2013APASS
DetailsRock A. Hudson
If you could call me in advance so I can bring my ladder that would be great. Thanks Phone #: ###-#### >> Inspection requested via web by Neal Rumsey Rough in ok cover p/s u/g n ok
Rough-In Permanent Service10/8/201310/8/201310/8/2013PFAIL
DetailsRock A. Hudson
Phone #: ###-#### >> Inspection requested via web by Neal Rumsey
300.4 Bored holes less than 1 1/4" from stud surface shall be protected from physical damage. NM cable and low volt shall be protected.
210.52- Receptical outlets shall be installed so that no point measured along floor line is more than 6' from outlet. Master bed and family rm.
210.52- Receptical outlet shall be installed with in 6' of door opening measured along floor line. Down bed pocket door to bath.
* Out patio ceilings covered prior to inspection.