Final | 11/15/2013 | 11/15/2013 | 11/15/2013 | P | PASS |
Bob Reichert
|
|
|
Phone #: ###-#### >> Inspection requested via web by Brad Baker corrections made, ok final
|
Final | 11/8/2013 | 11/12/2013 | 11/12/2013 | A | FAIL |
Bob Reichert
|
|
|
Phone #: ###-#### >> Inspection requested via web by Brad Baker called, NEC 408.4 shall provide correct circuit schedule, 110.26 shall provide workspace about electrical equipment, both width and depth
|
Electrical Rough-In | 10/17/2013 | 10/17/2013 | 10/17/2013 | P | PASS |
Bob Reichert
|
|
|
Phone #: ###-#### >> Inspection requested via web by Brad Baker ri ok
|
Electrical Rough-In | 10/16/2013 | 10/17/2013 | 10/17/2013 | A | FAIL |
Bob Reichert
|
|
|
They are open for business so any time is fine Phone #: ###-#### >> Inspection requested via web by Brad Baker called, NEC 300.4(D) mc cable shall be 1 1/4" from edge of framing member
|