Information based on query as of Friday, June 28, 2024.
Permit Information
Permit NumberELE13-03022
StatusFinaled
Name ULTIMATE ELECTRIC LLC
Site Address 4273 N ARROW VILLA WAY
Project Name 
Customer Number 
ePlanReviewNo
Description
Electrical Permit - New: New home wiring
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final2/13/20142/14/20142/14/2014APASS
DetailsBob Reichert
Garage code 3283 Phone #: ###-#### >> Inspection requested via web by daniel bibikov ok final
Final2/5/20142/6/20142/6/2014AFAIL
DetailsRock A. Hudson
Phone #: ###-#### >> Inspection requested via web by daniel bibikov 210.8- All garage 120 volt 15 and 20 amp recepticals shall have GFCI protection.
406.5- Switches and recepticals shall have faceplates installed.
406.4- Receptical yoke shall be rigidly mounted to box or box cover.
314.20- Boxes set back 1/4" or more shall have spark or extension ring.
Rough-In Permanent Service11/1/201311/1/201311/1/2013PPASS
DetailsRock A. Hudson
Phone #: ###-#### >> Inspection requested via web by daniel bibikov Rough in ok cover p/s u/g n ok
Rough-In Permanent Service10/31/201311/1/201311/1/2013AFAIL
DetailsRock A. Hudson
Corrections not complete, nail plate above pantry door and closet in spare bed and secure NM cable above trans box in garage
Rough-In Permanent Service10/30/201310/31/201310/31/2013AFAIL
DetailsRock A. Hudson
Phone #: ###-#### >> Inspection requested via web by daniel bibikov 300.4 NM csble shall be protected from physical damage where 1 1/4" not maintained from stud surface.
334.30- NM cabe shall be secured with in 12" of entering box with clamp, 8" with out. NM cable shall not be stapled on edge.
BCC 4-05-23- It shall be unlawful to cover wiring before inspected.