Temporary Service | 11/15/2013 | 11/18/2013 | 11/18/2013 | A | PASS |
Daryl DeGrange
|
|
|
HP. Phone #: ###-#### >> Inspection requested via web by Sean DeLacy correction done, t/s o/h n ok
|
Temporary Service | 11/15/2013 | 11/15/2013 | 11/15/2013 | P | FAIL |
Daryl DeGrange
|
|
|
HP. Temp service. Phone #: ###-#### >> Inspection requested via web by Sean DeLacy Ground rod cut-off NEC Grounding electrode shall be at least 8ft. in contact with the soil.
|