Information based on query as of Friday, August 16, 2024.
Permit Information
Permit NumberELE13-03157
StatusFinaled
Name BENDER ELECTRIC SERVICES
Site Address 406 S VISTA AVE
Project Name 
Customer Number 
ePlanReviewNo
Description
Electrical Permit - New: Power to garage
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final7/25/20147/28/20147/28/2014APASS
DetailsRock A. Hudson
Phone #: ###-#### >> Inspection requested via web by kendall bender Final ok
Final7/25/20147/25/20147/25/2014PFAIL
DetailsRock A. Hudson
Phone #: ###-#### >> Inspection requested via web by kendall bender 210.8- All 15 and 20 amp 120 volt receptical outlets shall have GFCI protection.
110.26- Minimum work space of 30" wide and 36" deep shall beclear of vegetation in front of meter panel combo.
314.17- NM cable sheathing shall enter box by minimum of 1/4". Bay 4 opener outlet.
408-4- Circuit directory shall be complete.
Electrical Rough-In2/12/20142/12/20142/12/2014PPASS
DetailsDaryl DeGrange
Phone #: ###-#### >> Inspection requested via web by kendall bender Rough-in ok cover 5 bay garage
Electrical Rough-In11/12/201311/12/201311/12/2013PPASS
DetailsBob Reichert
Ufer at garage wall Phone #: ###-#### >> Inspection requested via web by kendall bender concrete encased electrode ok cover