DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final4/30/20144/30/20144/30/2014PPASS
DetailsRock A. Hudson
Phone #: ###-#### >> Inspection requested via web by ron spen cer Final ok
Final4/29/20144/29/20144/29/2014PFAIL
DetailsRex Boyles
Phone #: ###-#### >> Inspection requested via web by ron spen cer fix kitchen outlet to be GFci protected
Final12/23/201312/23/201312/23/2013ACANC
DetailsRock A. Hudson
Phone #: ###-#### >> Inspection requested via web by ron spen cer Needed rough in inspection
Rough-In Permanent Service12/23/201312/23/201312/23/2013PPASS
DetailsRock A. Hudson
Phone #: ###-#### >> Inspection requested via web by ron spen cer Rough in ok cover p/s u/g n ok
Electrical Rough-In12/20/201312/20/201312/20/2013PFAIL
DetailsRock A. Hudson
roughin and service inspection on house. roughin only for cover on detached garage. Phone #: ###-#### >> Inspection requested via web by ron spen cer 338 refers to 334 part to for support of SE cable. 334.30- SE Cable shall have supports not exceeding 4 1/2 feet.
300.4 Where NM cable is ran through bored holes which pass less than 1 1/4" from framing member surface cable shall be protected be nail plate.
334.30- NM cable shall be secured with in 12" of entering boxes.
334.30- Flat cables shall not be stapled on edge.
Garage OK cover