Final | 7/30/2014 | 7/31/2014 | 7/31/2014 | A | PASS |
Daryl DeGrange
|
|
|
Phone #: ###-#### >> Inspection requested via web by Spencer McLean final ok
|
Final | 7/23/2014 | 7/23/2014 | 7/23/2014 | P | NR |
Daryl DeGrange
|
|
|
Phone #: ###-#### >> Inspection requested via web by Spencer McLean Not ready
|
Permanent Service | 6/17/2014 | 6/17/2014 | 6/17/2014 | P | PASS |
Daryl DeGrange
|
|
|
Phone #: ###-#### >> Inspection requested via web by Spencer McLean Correction done p/s u/g n ok
|
Electrical Rough-In | 6/10/2014 | 6/11/2014 | 6/11/2014 | A | PASS |
Daryl DeGrange
|
|
|
>> Inspection requested via web by Spencer McLean Rough-in ok cover walls and hard lid.
|
Rough-In Permanent Service | 6/6/2014 | 6/6/2014 | 6/6/2014 | P | NR |
Bob Reichert
|
|
|
Please inspect for cover Phone #: ###-#### >> Inspection requested via web by Spencer McLean met contractor, shall install mud rings, provide 1 1/4" for mc cable, strap mc ,move duct over panels, provide proper pull box at service, shall not utilize u/g at north of entry- not deep and electrical contractor did not install, and already covered
|
Temporary Service | 3/6/2014 | 3/6/2014 | 3/6/2014 | P | PASS |
Daryl DeGrange
|
|
|
spencer Phone #: ###-#### corrections done, t/s u/g n ok
|
Temporary Service | 3/5/2014 | 3/6/2014 | 3/6/2014 | A | FAIL |
Daryl DeGrange
|
|
|
Please inspect the temporary power pole that is installed at the pad mount transformer on the East side of the site. Phone #: ###-#### >> Inspection requested via web by Spencer McLean NEC250.52(5) Grounding electrode shall not be less than 8 ft. in lenght. Full 8 ft in contact with the earth.
|