Permit NumberELE14-01095
StatusFinaled
Name TASKER ELECTRICAL CONSTRUCTION INC
Site Address 3088 S LINDSAY AVE
Project Name 
Customer Number 
ePlanReviewNo
Description
Electrical Permit - New: new home construction
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final6/30/20147/1/20147/1/2014APASS
DetailsRock A. Hudson
>> Inspection requested via web by Stacie Tasker Final ok
Final6/26/20146/27/20146/27/2014AFAIL
DetailsRock A. Hudson
Phone #: ###-#### >> Inspection requested via web by Stacie Tasker 210.12- All 15 and 20 amp 120 volt outlets shall have AFCI protection.
210.52(C)(1)- A receptical outlet shall be located with in 24" of left side of range.
210.63- A 120 volt 15 or 20 amp receptical outlet shall be located with in 25' of AC unit accessible from outside.
406.11- All areas specified in 210.52 all 15 and 20 amp 120 volt receptical outlet shall be tamper resistant type.
Electrical Rough-In5/2/20145/5/20145/5/2014APASS
DetailsRock A. Hudson
>> Inspection requested via web by Stacie Tasker rough in ok cover
Permanent Service5/5/20145/5/20145/5/2014PPASS
DetailsRock A. Hudson
>> Inspection requested via web by Stacie Tasker p/s u/g n ok
Electrical Rough-In5/1/20145/2/20145/2/2014AFAIL
DetailsRock A. Hudson
Phone #: ###-#### >> Inspection requested via web by Stacie Tasker Idaho power requires an expansion joint on all underground service entrance conduits for residential.
250.52(B)(1)- Metal gas piping systems shall not be used as grounding electrodes. 250.104(B) not enforced in Idaho.
334.30- NM cable shall be secured with in 12" of box.
210.52- Up bedroom, any wall space 24" and wider shall have receptical outlet installed.