Information based on query as of Wednesday, July 17, 2024.
Permit Information
Permit NumberELE14-01124
StatusFinaled
Name ELECTRICAL CONTROLS & INSTRUMENT
Site Address 517 N HAINES ST
Project Name 
Customer Number 
ePlanReviewNo
Description
Electrical Permit - Alteration: new service and interior kitchen, bath, bed remodel
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final11/11/201411/12/201411/12/2014APASS
DetailsRex Boyles
call for access if not open Phone #: ###-#### Inspection requested via web by shane vigil final ok
Final11/5/201411/6/201411/6/2014PFAIL
DetailsRex Boyles
back slider open. Phone #: ###-#### Inspection requested via web by shane vigil Loose receptacles in kitchen and upst. bath. 406.11-in all areas listed in 210.52 all 125 volt receptacles shall be tamper resistant.ok not to have tamper resistant in area of house not worked on. 314.20-face of box shall be 1/4inch or less to finsh surface(kitchen backsplash) or use box extensions. 210.12(B)-AFCI protection required in all bedrooms. ok not to have afci in old existingbdrms. 210.52(E)(1)-at least one receptacle outlet accessable from grade level required at back of dwelling.ok not to install in front. 210.8(A)(7)- GFCI protection required where receptacles are installed within 6 foot of sink (laundry room). 410.10(A)-recessed fixture in shower not rated for wetlocation.basement bdrm. closet fixture has no globe.
Electrical Rough-In5/21/20145/22/20145/22/2014APASS
DetailsBob Reichert
call for key location Phone #: ###-#### >> Inspection requested via web by shane vigil corrections made, ri ok
Electrical Rough-In5/21/20145/21/20145/21/2014AFAIL
DetailsRex Boyles
ELE-INSPECTOR 334.30 secure nm cable min. every 4 1/2 feet above sub-panel in hall. 300.4D 11/4 min to nm cable from edge of framing. under subpanel and 1/0ser in kitchen. Exhaust fan not installed and waterbond ground needs to be connected.
Permanent Service5/5/20145/6/20145/6/2014APASS
DetailsRex Boyles
Service only, rough in and sub panel to be done after. Phone #: ###-#### >> Inspection requested via web by shane vigil p/s o/h rec ok please use "rigid" strap for rigid riser when you get the chance