Permit Information
Permit NumberELE14-01191
StatusFinaled
Name MARK HOYT
Site Address 895 N LANDER ST
Project NameADU / DUPLEX
Customer Number 
ePlanReviewNo
Description
electrical work for new ADU/Duplex
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final11/10/201411/12/201411/12/2014PPASS
DetailsCevyn Recla
as early PM as possible please // Mark Phone #: ###-####
Corrections made. FInal OK
Final11/7/201411/10/201411/10/2014PFAIL
DetailsCevyn Recla
Mark Phone #: ###-####
Art. 100, disconnecting means for water heater
406.12A Tamper resistant receptacles required for dwelling unit
210.52B2 Kitchne small applinance circuit can not feed outdoor receptacle
Permanent Service10/1/201410/2/201410/2/2014APASS
DetailsRock A. Hudson
Mark Phone #: ###-#### p/s o/h n ok
Electrical Rough-In9/12/20149/15/20149/15/2014APASS
DetailsRock A. Hudson
Mark-woluld like later in the AM if posssible Phone #: ###-#### Clamping connector shall be installed on back of meter for SER entrance to can. Addition rough in ok cover
Conference9/11/20149/11/20149/11/2014PDONE
DetailsRex Boyles
mark Phone #: ###-#### discuss 400 amp meter with bypass. Told mark to confirm its ok. discuss bending 300 alum in 2x6 wall, discuss 300 alum in raceway thru attic ,is ok
Conference8/28/20148/29/20148/29/2014ADONE
DetailsRex Boyles
mark Phone #: ###-#### discuss 400 amp service and circuitry
Electrical Rough-In8/15/20148/18/20148/18/2014ACANC
DetailsRock A. Hudson
Actually wants a conference----Mark Phone #: ###-#### Conference requested
Conference8/18/20148/18/20148/18/2014PDONE
DetailsRock A. Hudson
Actually wants a conference----Mark Phone #: ###-#### Discussed minimum kitchen counter top circuits and receptical layout,service grounding, direct burial depth, dedicated bath receptical circuit. overhead service entrance clearances.