Final | 6/4/2014 | 6/4/2014 | 6/4/2014 | P | PASS |
Rock A. Hudson
|
|
|
Conf. only final ok
|
Conference | 5/22/2014 | 5/23/2014 | 5/23/2014 | A | FAIL |
Rock A. Hudson
|
|
|
need conference on what is going to be required to repair wiring in kitchen due to fire. Please call Andy @ ###-#### to set time to meet. Phone #: ###-#### >> Inspection requested via web by Andy Rose Due to small kitchen fire ceiling and some drywall has been removed in kitchen. BCC 4-05-32- Code violation not to be retained. When altering pre-existing wiring the electrical witing in close proximity shall be in accordance with present code. 1- NEC 210.8 All kitchen counter top receptical outlets shall have GFCI protection. 2- NEC 210.11(C)(1)- Kitchen counter top receptical outlets shall be fed by a minimum of 2 20 amp small appliance circuits that shall have no other outlets. BCC 4-05-31(C)- Unfused conductors shall not enter a structure. Main fused disconnecting means shall be installed outside as per NEC 230.70 and 230.71. NEC 110.26- Minimum work space shall be 30" wide and 36" deep at panel location.
|