Final | 1/14/2015 | 1/14/2015 | 1/14/2015 | P | PASS |
Cevyn Recla
|
|
|
Key is in the same location
Call Tim if needed
Thank you Phone #: ###-#### Inspection requested via web by John Harvey no inspection record of floor heat under tile, cable that can be seen is listed product corrections made, final OK
|
Final | 1/12/2015 | 1/13/2015 | 1/13/2015 | A | FAIL |
Cevyn Recla
|
|
|
Call Tim if any problems
Key is above the small window on the front porch Phone #: ###-#### Inspection requested via web by John Harvey left notice with building contractor 210.8A 2 GFI protection required, all receptacles in garage 210.8A7 GFI protection require all receptacles within 6 foot of sink 334.12 NM calbe not permitted in wet locations 422.31 Disconnecting means required for all permanently installed appliances 210.52 C 3 Penninsula receptacle required 356.30 LFNC shall be secured within 12 inches of boxes 408.4 Circuit directory shall be legibly marked 110.3 B Installation and use, items shall be installed according to instructions, fllor heat thermostat not functioning, could not test GFI
|
Electrical Rough-In | 12/24/2014 | 12/26/2014 | 12/26/2014 | A | PASS |
Cevyn Recla
|
|
|
corrections made, garage r/i ok to cover
|
Electrical Rough-In | 12/23/2014 | 12/24/2014 | 12/24/2014 | A | FAIL |
Cevyn Recla
|
|
|
Garage rough in only
Tim is general contractor. Contact if needed
Phone #: ###-#### Inspection requested via web by John Harvey left voicemail at number provided 334.30 NM shall be secured by staple, cable tie, strap, or similar fitting designed not to damage cable 3334.80 ampacity of nm, bundling of romex through holes, no more than six current carrying conductors allowed 250.68 A grounding electrode connection shall be accessible 300.4 NM through bored holes shall have protection where hole is less than 1 1/4 inch from framing member edge 352.24 Rigid PVC bends shall be made so conduit is not damaged BCC, all items shall be ready for inspection type that is being made, there are romex and box hanging out of wall.
|
Final | 11/7/2014 | 11/7/2014 | 11/7/2014 | P | CANC |
Cevyn Recla
|
|
|
Tim-perm. service for garage Phone #: ###-####
Wrong inspection called in
|
Permanent Service | 11/7/2014 | 11/7/2014 | 11/7/2014 | P | PASS |
Cevyn Recla
|
|
|
Tim-perm. service for garage Phone #: ###-####
PS, OH, N , OK
|
Temporary Service | 9/12/2014 | 9/12/2014 | 9/12/2014 | P | PASS |
Rex Boyles
|
|
|
Temp service to prepare for garage demo. Contact builder at above number. Phone #: ###-#### Inspection requested via web by John Harvey t/s o/h n ok (existing service drop might not be long enough)
|
Electrical Rough-In | 7/14/2014 | 7/15/2014 | 7/15/2014 | P | PASS |
Rex Boyles
|
|
|
John is out of town. House is open. Call Tim if there are any issues
Phone #: ###-#### >> Inspection requested via web by John Harvey r/i ok
|