Information based on query as of Wednesday, July 3, 2024.
Permit Information
Permit NumberELE14-01948
StatusFinaled
Name TRI STATE ELECTRIC
Site Address 1105 S LA POINTE ST
Project NameWest Sherwood Apartments
Customer Number 
ePlanReviewNo
Description
ground work for future apartments, race way and stub up $10,000.00
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final7/24/20157/24/20157/24/2015APASS
DetailsRex Boyles
Contact: Jeremy Thornock Phone #: ###-#### Inspection requested via web by Deb Gooden final ok on original groundwork permit
Electrical Rough-In10/14/201410/14/201410/14/2014PFAIL
DetailsRock A. Hudson
###-#### Concrete encased rough in. 250.52(A)(3)- South east service, concrete encased will not work do to rebar and 20" of wire located on top of plastic moisture barrier, not tied to footing or foundation rebar. It shall be in direct contact with earth.
Electrical Rough-In10/13/201410/14/201410/14/2014ANR
DetailsRock A. Hudson
Contact: Jeremy Thornock. Ufer inspection please Phone #: ###-#### Inspection requested via web by Deb Gooden Wire removed no rebar in place
Electrical Rough-In10/6/201410/7/201410/7/2014APASS
DetailsRock A. Hudson
Contact: Jeremy Thornock... underground rough-in inspection please Phone #: ###-#### Inspection requested via web by Deb Gooden Underground for south east electrical room rough in ok cover
Electrical Rough-In9/26/20149/29/20149/29/2014APASS
DetailsRock A. Hudson
Contact Name: Jeremy Thornock
Underground Inspection Phone #: ###-#### Inspection requested via web by Deb Gooden Northwest electrical room underground rough in ok cover
Final7/17/20147/18/20147/18/2014PNR
DetailsDaryl DeGrange
Contact: Jeremy Thornock. inspection for 2 ufer grounds Phone #: ###-#### >> Inspection requested via web by Deb Gooden Not ready for final at this time.
Electrical Rough-In7/18/20147/18/20147/18/2014PPART
DetailsDaryl DeGrange
Contact: Jeremy Thornock. inspection for 2 ufer grounds Phone #: ###-#### >> Inspection requested via web by Deb Gooden Rough-in ok cover 1 of 2 concrete encased electrodes, northwest corner