Information based on query as of Wednesday, July 3, 2024.
Permit Information
Permit NumberELE14-02818
StatusFinaled
Name ALPINE ELECTRIC
Site Address 2619 N 24TH ST
Project Name 
Customer Number 
ePlanReviewNo
Description
Permit for final trim in kitchen
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final10/17/201410/21/201410/21/2014PPASS
DetailsRock A. Hudson
JR Phone #: ###-####
Final OK kitchen
Final10/13/201410/15/201410/15/2014PFAIL
DetailsRock A. Hudson
JR Phone #: ###-#### 406.4(D)- All grounding type receptical outlets shall be GFCI protected that are installed on ungrounded circuits. refrigerator.
406.6- All receptical outlets and switches shall have covers. Receptical in bed room shall be tight to box and covered.
Corrections not complete.
Contact A-1 electric. Permit # ele14-01322 for items outside kitchen. Previous contractor no longer working on project. This permit for kitchen only. This contractor to make sure covers are install and recepticals secured to box in bed.
Final10/9/201410/10/201410/10/2014PFAIL
DetailsBob Reichert
Anastacio Phone #: ###-#### called, left correction notice, NEC 406.11 all receptacles shall be tamper resistant, 110.3 receptacles shall operate per listings, BCC shall wire hood, all receptacle and switch covers shall be installed, NOTE: shall have other contractor call for final or change room count for this permit, and check all house, not just kitchen