Final | 4/17/2015 | 4/17/2015 | 4/17/2015 | A | PASS |
Daryl DeGrange
|
|
|
Garage code 0500. Thank you Phone #: ###-#### Inspection requested via web by daniel bibikov correction done, final ok
|
Final | 4/16/2015 | 4/16/2015 | 4/16/2015 | P | FAIL |
Rock A. Hudson
|
|
|
Garage code 0500. Corrections are complete. Thank you Phone #: ###-#### Inspection requested via web by daniel bibikov Missed upstairs bed closet luminaire top of stairs straight ahead. 410.16- All closet luminaires shall have enclosed lamps
|
Final | 4/10/2015 | 4/10/2015 | 4/10/2015 | P | FAIL |
Rock A. Hudson
|
|
|
Garage code 5550. Thank you Phone #: ###-#### Inspection requested via web by daniel bibikov 110.3 receptacle outlet not working in finished portion of basement hall. 210.8- GFCI protection shall be provided for all 120 volt receptacle outlets installed in unfinished portion of basement. 410.10(D)- Luminaire installed over edge of shower shall be rated for damp location. 410.16- All closet luminaires shall have totally enclosed lamps. 314.15- Light openings on outside of house shall have blank covers rated for damp locations. 334.80- #6 NM cable for hot tub ampacity shall not exceed 55 amps. Prewire shall have GFCI protection. 408.7- Hot tub panel unused openings shall be closed. 314.23- Out light boxes shall be securely mounted.
|
Electrical Rough-In | 1/30/2015 | 1/30/2015 | 1/30/2015 | P | PASS |
Cevyn Recla
|
|
|
floor heat master bath floor heat ok to cover
|
Permanent Service | 1/30/2015 | 1/30/2015 | 1/30/2015 | P | DONE |
Cevyn Recla
|
|
|
Dillion Phone #: ###-#### left message, Perm service was done in November, checked site, not sure what inspection was wanted,
|
Rough-In Permanent Service | 11/21/2014 | 11/21/2014 | 11/21/2014 | P | PASS |
Cevyn Recla
|
|
|
Phone #: ###-#### Inspection requested via web by daniel bibikov corrections made. RI OK PS, UG, N, OK
|
Rough-In Permanent Service | 11/20/2014 | 11/21/2014 | 11/21/2014 | A | FAIL |
Cevyn Recla
|
|
|
Phone #: ###-#### Inspection requested via web by daniel bibikov still missing nail plates.
300.4A1 Nail plates required-bored holes less than 1-1/4 inch from edge of framing member
|
Rough-In Permanent Service | 11/20/2014 | 11/20/2014 | 11/20/2014 | P | FAIL |
Cevyn Recla
|
|
|
Call daniel ###-####. The basement bath gfi splits from 12/3 home run from float switch Phone #: ###-#### Inspection requested via web by daniel bibikov Not all corrections have been fixed. Ground clamp is still loose, nail plates are still missing
|
Rough-In Permanent Service | 11/19/2014 | 11/19/2014 | 11/19/2014 | P | FAIL |
Cevyn Recla
|
|
|
Phone #: ###-#### Inspection requested via web by daniel bibikov called Daniel 210.52A2(1)outlet required within first six feet of wall space 21052A2 outlet required wall space 2 foot or greater 210.11C3 bath outlet circuit shall supply not other outlets 210.52E3 required outlets, balconies shall have at least one receptacle 210.52H. Hallway 10 foot or greater shall have at least one receptacle 300.4A1 Nail plates required-bored holes less than 1-1/4 inch from edge of framing member 110.12 Mechanical execution of work, ground clamp is loose at grounding electrode 250.70 Only one wire allowed under ground clamp 250.68A- Ground clamp to be accessible
|