Permit Information
Permit NumberELE14-03369
StatusFinaled
Name CAMAS ELECTRIC CONTRACTING
Site Address 3532 W BELLOMY LN
Project Name 
Customer Number 
ePlanReviewNo
Description
Electrical Permit - New: Electrical wiring in new residence
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final4/24/20154/24/20154/24/2015PPASS
DetailsRex Boyles
Mark Phone #: ###-#### final ok
Final4/23/20154/23/20154/23/2015PNH
DetailsRex Boyles
Mark Phone #: ###-#### no access
Permanent Service2/5/20152/5/20152/5/2015PPASS
DetailsCevyn Recla
Mark Phone #: ###-####
PS, OH, N, OK
Rough-In Permanent Service2/5/20152/5/20152/5/2015PCANC
DetailsCevyn Recla
Mark Phone #: ###-####
Needed PS inspection
Electrical Rough-In12/17/201412/17/201412/17/2014PPASS
DetailsCevyn Recla
Mark Phone #: ###-####
corrections made, RI OK
Electrical Rough-In12/16/201412/17/201412/17/2014AFAIL
DetailsCevyn Recla
Mark Phone #: ###-####
Daryl DeGrange spoke to contractor, not all corrections have been addressed.
Electrical Rough-In12/11/201412/12/201412/12/2014AFAIL
DetailsCevyn Recla
Phone #: ###-#### Inspection requested via web by Mark Hansen
210.17 Electric vehicle branch circuit shall supply no other outlets
210.52A.1 spacing, no wall space greater than 6 foot from a receptacle
210.52C.1 wall countertop space, no point greater than 24 inches from a receptacle
210.52 I dining receptacle shall be supplied from 20 amp small appliance circuit
300.13B Grounded conductor multi wire circuit, shall not depend on device
300.4 nm cable through bored hole less than 1 1/4 inch from framing member edge shall be protected
The range box is rated for up to a #10 wire, you need to use a box rated for the wire installed.