Temporary Service | 12/10/2014 | 12/11/2014 | 12/11/2014 | P | PASS |
Bob Reichert
|
|
|
Phone #: ###-#### Inspection requested via web by Kerri Hamilton corrections made, t/s u/g n ok
|
Temporary Service | 12/9/2014 | 12/10/2014 | 12/10/2014 | A | FAIL |
Bob Reichert
|
|
|
Phone #: ###-#### Inspection requested via web by Kerri Hamilton met electrician, left correction notice, NEC 590.6(B)(1) shall provide gfci protection for cable, 400.5(A) minimum size #4 type so for 60A service, 400.10 shall supply strain relief, 1120.12(A) close unused openings at trailer, 408.4 label circuits, 230.42 shall provide 60A service to trailer, 352.10(F) exposed pvc shall be schedule 80
|