DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final2/17/20152/17/20152/17/2015PPASS
DetailsCevyn Recla
Garage code 0500
Thank you Phone #: ###-#### Inspection requested via web by daniel bibikov
corrections made, Final OK
Final2/13/20152/13/20152/13/2015PFAIL
DetailsRock A. Hudson
Garage code 0500 Phone #: ###-#### Inspection requested via web by daniel bibikov
110.12(B)- Installation not complete. Kitchen outlets not working.
314.25- All boxes shall have covers. Switch under stairs.
Rough-In Permanent Service12/19/201412/19/201412/19/2014APASS
DetailsRock A. Hudson
Phone #: ###-#### Inspection requested via web by daniel bibikov Rough in ok cover p/s u/g n ok
Rough-In Permanent Service12/17/201412/18/201412/18/2014AFAIL
DetailsRock A. Hudson
Phone #: ###-#### Inspection requested via web by daniel bibikov
300.4(B)- Listed bushings shall be installed in holes in metal side of furnace.
334.30- NM cable shall be secured within 12" of boxes.
320.23- Cables shall be protected with in 7' of attic access.
314.17- NM cable sheathing shall enter box knock out a minimum of 1/4".
Temporary receptical outlets need installed. Can't approve a service with stripped wires hanging out of boxes.