Final | 3/30/2015 | 3/31/2015 | 3/31/2015 | A | PASS |
Rock A. Hudson
|
|
|
Ron Phone #: ###-#### Final ok
|
Final | 3/26/2015 | 3/26/2015 | 3/26/2015 | P | FAIL |
Rock A. Hudson
|
|
|
code 5151enter Phone #: ###-#### Inspection requested via web by ron spen cer 210.12- All 15 and 20 amp 120 volt outlets shall have AFCI protection. Master and smokes. 408.4- Master bed miss labeled. 110.3 Washer receptacle reverse polarity. 210.8- All 120 volt recetacles located with in 6' of sink shall have GFCI protection. Back sid of kit sink.
|
Permanent Service | 1/21/2015 | 1/21/2015 | 1/21/2015 | P | PASS |
Rock A. Hudson
|
|
|
ron ###-#### p/s u/g n ok
|
Permanent Service | 1/20/2015 | 1/20/2015 | 1/20/2015 | P | FAIL |
Rock A. Hudson
|
|
|
310.15(B)(7)- In no case shall the service entrance conductors be sized less than 83% of the service rating. 125 amp x 83%= 103.75 amps. Table 310.15(B)(16)- 75* #2 minimum size required.
|
Electrical Rough-In | 1/20/2015 | 1/20/2015 | 1/20/2015 | P | PASS |
Rock A. Hudson
|
|
|
Rough in ok cover
|
Rough-In Permanent Service | 1/20/2015 | 1/20/2015 | 1/20/2015 | P | CANC |
Rock A. Hudson
|
|
|
See rough in
|