Permit Information
Permit NumberELE15-01725
StatusFinaled
Name ULTIMATE ELECTRIC LLC
Site Address 6672 W WINSTON LN
Project Name 
Customer Number 
ePlanReviewNo
Description
New: new 4 plex wiring
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final8/13/20158/14/20158/14/2015APASS
DetailsRock A. Hudson
Phone #: ###-#### Inspection requested via web by daniel bibikov Final ok
Final8/13/20158/13/20158/13/2015PFAIL
DetailsRock A. Hudson
Phone #: ###-#### Inspection requested via web by daniel bibikov 210.8- GFCI not working in space 100, unable to test. 408.4- label house panel and check labels in rest 101 dryer and above.
Permanent Service6/15/20156/15/20156/15/2015PPASS
DetailsEric Story
Phone #: ###-#### Inspection requested via web by daniel bibikov p/s u/g n ok
Electrical Rough-In6/11/20156/11/20156/11/2015PPASS
DetailsRock A. Hudson
Phone #: ###-#### Inspection requested via web by daniel bibikov Rough in ok cover
Final6/11/20156/11/20156/11/2015APASS
DetailsRock A. Hudson
Phone #: ###-#### Inspection requested via web by daniel bibikov Rough in ok cover
Electrical Rough-In6/10/20156/10/20156/10/2015AFAIL
DetailsRock A. Hudson
Inspection requested via web by daniel bibikov 250.24(A)(5)- Grounded conductor shall not be connected to non current carrying metal parts on load side of service disconnecting means. remove bonding screw in panel lower left unit.
300.4- NM cable shall be protected from physical damage when ran through bored holes that do not maintain 1 1/4" from framing surface. 45 degree drill corners, upper plates shallow or angled holes.