Information based on query as of Thursday, July 4, 2024.
Permit Information
Permit NumberELE15-01795
StatusFinaled
Name A-1 ELECTRIC
Site Address 448 S WHISPERWOOD WAY
Project Name 
Customer Number 
ePlanReviewNo
Description
Complete Installation: install electrical system
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final9/15/20159/16/20159/16/2015APASS
DetailsRock A. Hudson
Dan Phone #: ###-#### Inspection requested via web by Dan Hobdey Final ok
Final9/14/20159/15/20159/15/2015AFAIL
DetailsRock A. Hudson
Dan Garage code- 1234 Phone #: ###-#### Inspection requested via web by Dan Hobdey 210.23(A)(2)- Vac system fastened in place exceeds 50 percent of branch circuit in garage so dedicated ciruit required. 210.52- Any wall space 24" or wider shall have a receptacle outlet. 230.70(B)- Each service disconnnect shall be permanently marked to identify it as a service disconnect. 410.10(D)- Recessed can trim main bath over threshold of tub shower shall be listed for damp locations.
Rough-In Permanent Service6/17/20156/17/20156/17/2015PPASS
DetailsEric Story
Inspection requested via web by Dan Hobdey rough-in ok cover p/s u/g n ok
Rough-In Permanent Service6/16/20156/16/20156/16/2015PFAIL
DetailsRock A. Hudson
Dan Phone #: ###-#### Inspection requested via web by Dan Hobdey 300.4- NM calbe shall not be ran where it may be subject to physical damage. master bed firewall on clips.
334.30- NM cable shall be secured within 12" of smoke in masteer bed.
334.80- Where 2 or more NM cables are ran through bored holes without maintaining spacing derating calculations shall apply.
BCC- Firewall shall be clear for fire barrier. Wiring shall be relocated from behind studs in firewalls in master bed and garage.