Permit Information
Permit NumberELE15-02615
StatusFinaled
Name ROBERTSON ELECTRIC
Site Address 6363 W EMERALD ST Unit: 103
Project Name 
Customer Number 
ePlanReviewNo
Description
Alteration: Installing new lights and installing new switches and plugs
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final12/29/201512/29/201512/29/2015PPASS
DetailsRock A. Hudson
Phone #: ###-#### Inspection requested via web by Zane Robertson
No card posted. ETL listing on over chair luminaires. Final ok
Final12/28/201512/29/201512/29/2015AFAIL
DetailsBob Reichert
Phone #: ###-#### Inspection requested via web by Zane Robertson corrections not made, called, lights over patient chair not listed, gfci not working in south patient area, can't reset gfci in bath, will fix and recall
Final12/28/201512/28/201512/28/2015PFAIL
DetailsRex Boyles
Phone #: ###-#### Inspection requested via web by Zane Robertson equipment listed, floor boxes fed with proper wiring. BUT 517.18(B)- all receptacles in procedure rooms shall be listed "hospital grade" and shall be so identified. 110.16-Arc flash warning label required on loadcenters. Update panel schedule
Final12/23/201512/24/201512/24/2015ANR
DetailsBob Reichert
Phone #: ###-#### Inspection requested via web by Zane Robertson called, covers off plugs and switches, shall show listings for equipment, check on hospital grade receptacles with 327
Electrical Rough-In10/7/201510/8/201510/8/2015PPASS
DetailsRock A. Hudson
Rough for 4 dental stations Phone #: ###-#### Inspection requested via web by Zane Robertson Floor receptacle outlets fed with ENT. Made note on correction from previous inspection to remove power cords that have been fished down interior wall and to refeed floor boxes for dental chairs with an approved method. Walls and patches rough in ok cover
Electrical Rough-In9/21/20159/21/20159/21/2015PFAIL
DetailsRock A. Hudson
Electrical rough in for relocated walls Phone #: ###-#### Inspection requested via web by Zane Robertson
400.8(2)- Flexible cords shall not be ran through holes in walls.
517.13- Branch circuits serving patient care areas shall be provided with and effective ground fault path by installation in a metal raceway system, or cable having a metal armor or sheath assembly.