Permit Information
Permit NumberELE15-03182
StatusFinaled
Name ULTIMATE ELECTRIC LLC
Site Address 800 N MAPLE GROVE RD
Project Name 
Customer Number 
ePlanReviewNo
Description
New: New 4 plex wiring
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final12/10/201512/10/201512/10/2015PPASS
DetailsRock A. Hudson
Phone #: ###-#### Inspection requested via web by daniel bibikov
Final ok
Final12/9/201512/9/201512/9/2015AFAIL
DetailsRock A. Hudson
Phone #: ###-#### Inspection requested via web by daniel bibikov
110.3- Electrical devices shall be connected as per manufacturers instructions. 202 kit GFCI not working, 202 3-way miss wire.
210.52(A)- A receptacle outlet shall be located with in 6' of back door. 101, 102
210.52(C)(1)- A receptacle outlet shall be located with in 24" of start of counter top between sink and wall. 201, 202
Rough-In Permanent Service10/7/201510/7/201510/7/2015APASS
DetailsRock A. Hudson
Phone #: ###-#### Inspection requested via web by daniel bibikov Rough in ok cover p/s u/g n ok
Rough-In Permanent Service10/6/201510/6/201510/6/2015AFAIL
DetailsRock A. Hudson
Phone #: ###-#### Inspection requested via web by daniel bibikov
334.30- NM cable shall be secured with in 12" of a box and with in 4 1/2' of upper plate. 201 bed and 102 bath.
* mudring missing of up bath 202