Permit Information
Permit NumberELE15-03579
StatusFinaled
Name MICHAEL BELT
Site Address 2806 N MCKINNEY ST
Project Name 
Customer Number 
ePlanReviewNo
Description
homeowner permit; Kitchen, bedroom, and downstairs laundry
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final2/17/20162/18/20162/18/2016APASS
DetailsRock A. Hudson
Phone #: 6311362 >> Inspection requested via mobile web by Mike Final ok
Final2/16/20162/17/20162/17/2016AFAIL
DetailsRock A. Hudson
Phone #: 6311362 >> Inspection requested via mobile web by Mike
Owner installed floor heat in baths on main floor and basement without having inspected. Not having removed but shall have GFCI protection as per NEC 210.8
Electrical Rough-In11/6/201511/6/201511/6/2015PPASS
DetailsRock A. Hudson
Rough in ok cover
Electrical Rough-In11/5/201511/5/201511/5/2015PFAIL
DetailsRock A. Hudson
Michael Phone #: ###-####
210.52- Shall have receptacle outlet located with in 24" of left side of range.
250.64(C)- Splice for grounding electode conductor shall be with irriversible connector listed.
Wiring for smoke detectors shall be completed.
Electrical Rough-In11/4/201511/4/201511/4/2015PCANC
DetailsEric Story
homeowner is out of town but cousion will meet you there. Jay ###-#### needed conference
Conference11/4/201511/4/201511/4/2015PDONE
DetailsEric Story
homeowner is out of town but cousion will meet you there. Jay ###-#### met with owners cousin and discussed panel location in a fire wall, bringing panel up to code for grounding with 2 ground rods,and nailplating wires within 1 1/4" of framing member. Requested homeowner be onsite for rough-in inspection