Information based on query as of Wednesday, July 17, 2024.
Permit Information
Permit NumberELE15-03849
StatusFinaled
Name HOMETOWN ELECTRIC
Site Address 2581 S BROADWAY AVE
Project NameJacksons Broadway
Customer Number 
ePlanReviewNo
Description
Addition: Demo existing building wire new building , rewire canopy and fuel system
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final4/14/20164/14/20164/14/2016PPASS
DetailsRex Boyles
Seal coduits Phone #: ###-#### Inspection requested via web by Stan Woodward seal offs done and lockoffs on vacuums installed final ok
Final4/13/20164/13/20164/13/2016PPART
DetailsRex Boyles
Final Phone #: ###-#### Inspection requested via web by Stan Woodward partial final-everything finaled except seal offs for pumps temp. occupancy ok
Electrical Rough-In3/29/20163/30/20163/30/2016APASS
DetailsRex Boyles
Ceiling cover Phone #: ###-#### Inspection requested via web by Stan Woodward r/i t grid ceilings ok
Rough-In Permanent Service2/26/20162/26/20162/26/2016PPASS
DetailsRex Boyles
Underground Phone #: ###-#### Inspection requested via web by Stan Woodward remainder of exterior underground raceways r/i ok 100% NOTE:NO P/S NEEDED ALREADY RECEIVED YESTERDAY
Rough-In Permanent Service2/25/20162/25/20162/25/2016PPASS
DetailsRex Boyles
Underground to tanks and service have the Arc fault labels installed Phone #: ###-#### Inspection requested via web by Stan Woodward r/i u.ground raceways from new bldg. out to fuel storage tanks and from existing pumps out to vault and from vault back to new bldg. ok 2" from new bldg. out to vaccums also ok to cover. p/s u/g n ok
Permanent Service2/18/20162/18/20162/18/2016PFAIL
DetailsRex Boyles
Phone #: ###-#### Inspection requested via web by Stan Woodward need available fault current 110.24(A)- service equipment in other than dwelling units shall be legibly marked in the field with the maximum available fault current including date and calculation.
Electrical Rough-In2/10/20162/10/20162/10/2016PPASS
DetailsRex Boyles
Cover for the walls Phone #: ###-#### Inspection requested via web by Stan Woodward r/i all walls and bath ceilings ok
Electrical Rough-In1/15/20161/15/20161/15/2016PPASS
DetailsRex Boyles
I would like to get a cover on the underground for the Car Wash at the Jacksons new Store on Broadway Phone #: ###-#### Inspection requested via web by Stan Woodward r/i underslab conduits in car wash ok
Electrical Rough-In1/7/20161/7/20161/7/2016APASS
DetailsRex Boyles
We would like an inspection for cover on our underground, we will need to uncover the slab site first thing in the morning, If possible could you come by after 10 in the morning to make sure its uncovered for you. Phone #: ###-#### Inspection requested via web by Stan Woodward r/i underslab raceways and floorboxes ok to cover
Electrical Rough-In12/4/201512/4/201512/4/2015PPASS
DetailsRex Boyles
Underground from temporary pole to store Phone #: ###-#### Inspection requested via web by Stan Woodward r/i t/ s conduit ok to cover
Conference12/2/201512/2/201512/2/2015PDONE
DetailsRex Boyles
Temporary underground to existing store and temp power Phone #: ###-#### Inspection requested via web by Stan Woodward discuss picking up existing conduit to re feed store with 200 amp temp. service. OK to use existing bldg. grounding electrode instead of equipt. grounding conductor with feeders for temp. power.