Permit Information
Permit NumberELE15-03858
StatusFinaled
Name ENERGY ENTERPRISE GROUP LLC
Site Address 733 S PIONEER ST
Project NamePayette Brewery
Customer Number600
ePlanReviewNo
Description
Alteration: Electrical for construction o new brewery
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final5/16/20165/17/20165/17/2016APASS
DetailsEric Story
Ryan Barnes
Please call 30 minutes in advance for access
Phone #: ###-#### Inspection requested via web by Kerri Hamilton
All canning areas where equipment has not been set will need seperate permit. final for this permit ok cover
Final5/6/20165/9/20165/9/2016APART
DetailsEric Story
We spoke with Rex and informed him that this needs to be a later AM inspection and he obliged. Thank you! Phone #: ###-#### Inspection requested via web by Kerri Hamilton all office areas and tasting bar ok to occupy, will still need to verify equipmment when is wired to innsure it is free of shorts and competed.
Permanent Service5/2/20165/3/20165/3/2016APASS
DetailsRex Boyles
Phone #: ###-#### Inspection requested via web by Kerri Hamilton p/s u/g n ok 120/240 volt 1 phase parking lot lighting service on northwest corner of bldg. ALSO:"partial final" rooftop final ok
Electrical Rough-In4/25/20164/26/20164/26/2016ACANC
DetailsEric Story
Phone #: ###-#### Inspection requested via web by Kerri Hamilton wrong permit called in
Electrical Rough-In4/22/20164/22/20164/22/2016PCANC
DetailsEric Story
Temp Occ and partial Occ Phone #: ###-#### Inspection requested via web by Kerri Hamilton needed partial final
Final4/22/20164/22/20164/22/2016PPART
DetailsEric Story
Temp Occ and partial Occ Phone #: ###-#### Inspection requested via web by Kerri Hamilton office areas walls ok to move furniture in tasting bar area and walk-in cooler ok for partial final
Electrical Rough-In4/21/20164/22/20164/22/2016AFAIL
DetailsEric Story
Temp Occ in Office and Occ in Tasting Room
Ryan Barnes
Phone #: ###-#### Inspection requested via web by Kerri Hamilton 210.8 (b)(5) receptacles located within 6' of a sink shall have GFCI protection 4-s are not rated in a damp location 422.51 vending machines manufactored after 2005 shall have a GFCI protected cord from manufacter cant not verify they are not on site
Conference4/20/20164/20/20164/20/2016PDONE
DetailsEric Story
Ryan Barnes Phone #: ###-#### Inspection requested via web by Kerri Hamilton discussed low volt wiring and items for temp oc
Conference3/23/20163/24/20163/24/2016ADONE
DetailsEric Story
Phone #: ###-#### Inspection requested via web by Kerri Hamilton discussed lockout for pumps and locations of disconnects
Electrical Rough-In3/24/20163/24/20163/24/2016PPASS
DetailsEric Story
Phone #: ###-#### Inspection requested via web by Kerri Hamilton bar area walls ok cover
Permanent Service3/9/20163/9/20163/9/2016PPASS
DetailsEric Story
Ryan Barnes Phone #: ###-#### Inspection requested via web by Kerri Hamilton 1200 amp p/s u/g n ok
Permanent Service3/7/20163/8/20163/8/2016PFAIL
DetailsEric Story
Ryan Barnes
Phone #: ###-#### Inspection requested via web by Kerri Hamilton 230.95 (c) ground fault protection required pryor to being energized
Electrical Rough-In2/19/20162/22/20162/22/2016PPASS
DetailsBob Reichert
Ryan Barnes
Phone #: ###-#### Inspection requested via web by Kerri Hamilton ok cover u/g for rv pad west side
Electrical Rough-In2/17/20162/18/20162/18/2016APASS
DetailsRock A. Hudson
Ryan Barnes
Phone #: ###-#### Inspection requested via web by Kerri Hamilton
Island not ready. Tasting room wall rough in ok cover
Electrical Rough-In2/1/20162/2/20162/2/2016APASS
DetailsEric Story
Ryan Barnes
Phone #: ###-#### Inspection requested via web by Kerri Hamilton boiler and electrical room ok cover
Electrical Rough-In1/26/20161/27/20161/27/2016APASS
DetailsEric Story
Phone #: ###-#### Inspection requested via web by Kerri Hamilton bathrooms hard lids ok cover
Electrical Rough-In1/23/20161/25/20161/25/2016PPASS
DetailsEric Story
Underground in tasting room Phone #: ###-#### Inspection requested via web by Kerri Hamilton underground for tasting room ok cover
Electrical Rough-In1/12/20161/13/20161/13/2016APASS
DetailsEric Story
Ryan Barnes Phone #: ###-#### Inspection requested via web by Kerri Hamilton walls only ok cover
Electrical Rough-In12/17/201512/18/201512/18/2015APASS
DetailsEric Story
Ryan Barnes
Phone #: ###-#### Inspection requested via web by Kerri Hamilton underground as per contractors print ok cover
Electrical Rough-In12/15/201512/16/201512/16/2015PPASS
DetailsEric Story
Ryan Barnes Phone #: ###-#### Inspection requested via web by Kerri Hamilton underground as per contrators print ok cover
Electrical Rough-In12/9/201512/10/201512/10/2015APASS
DetailsEric Story
Ryan Barnes Phone #: ###-#### Inspection requested via web by Kerri Hamilton underground for relocating panels ok cover