Permit Information
Permit NumberELE15-03952
StatusFinaled
Name R M E INC
Site Address 500 S CAPITOL BLVD
Project Name 
Customer Number 
ePlanReviewNo
Description
New: Install underground and electrical raceways with in foundation and podium.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final7/13/20177/14/20177/14/2017APASS
DetailsEric Story
Randy. Phone #: ###-#### Inspection requested via web by Sean DeLacy
Final ok
Final2/13/20172/13/20172/13/2017PNR
DetailsEric Story
Matt. Phone #: ###-#### Inspection requested via web by Sean DeLacy
Elevator room needs to be finished, 4th floor has reversed polarity from elevator on right side of hall room number 407/all panels shall be nand discconects labeled
Electrical Rough-In8/9/20168/10/20168/10/2016APASS
DetailsRock A. Hudson
Dave. Phone #: ###-#### Inspection requested via web by Sean DeLacy
Discussed need to 1 side drywall for firewalls between guest rooms. OK for firewalls only, will be called out to check progress. North and south exterior wall myrtle side 2nd floor and all of 4th floor fire lid corridor rough in ok cover
Electrical Rough-In7/25/20167/26/20167/26/2016ANH
DetailsRock A. Hudson
Dave. Phone #: ###-#### Inspection requested via web by Sean DeLacy
Called, left message, waited 10 minutes, must recall
Dave called and informed of a 1'x1' soffit that will be built around each room and that electrical not being ran through soffits until rooms are wired.
Electrical Rough-In7/7/20167/8/20167/8/2016APASS
DetailsDaryl DeGrange
Dave. Cover inspection on lids for units. Phone #: ###-#### Inspection requested via web by Sean DeLacy Rough-in ok cover 2nd &3rd floors hard lid ceilings
Electrical Rough-In6/23/20166/23/20166/23/2016APASS
DetailsRock A. Hudson
Dave. Cover inspection on 2nd floor. Phone #: ###-#### Inspection requested via web by Sean DeLacy
Sign off book not ready yet. 2nd floor corridor fire lid rough in ok cover
Conference5/10/20165/11/20165/11/2016ADONE
DetailsRex Boyles
Dave. Phone #: ###-#### Inspection requested via web by Sean DeLacy discuss installation of mc cable supported by listed caddy hangers with 7 cables in each is OK to do. Also issue with fire pump room with other systems in same room, 2hr ceiling being installed to eliminate problem also OK
Conference2/19/20162/22/20162/22/2016ADONE
DetailsRex Boyles
Dave Johnson is on site Phone #: ###-#### Inspection requested via web by Buster Bowen discuss fire pump requirementa and fire pump room requirements. Dave agrees to move upright switchgear section for fire pump from main electric room into "fire pump" room. Also they will move loadcenters, irrigation controller and generator transfer switch shown in fire pump room out of fire pump room. All other equipment associated with fire pump and domestic water, controls, etc. ok in fire pump room. No generator emergency back up power required for fire pump if utilities come in underground. NFPA20-4.12.1.1.4-rooms containing fire pumps shall be free from storage, equipment, and pentrations not essential to the operation of the pump and related components.
Conference2/17/20162/17/20162/17/2016PDONE
DetailsRex Boyles
Dave. Fire Pump service conference. Phone #: ###-#### Inspection requested via web by Sean DeLacy Asked Dave to run separate raceway from utility transformer straight to fire pump controller. Also there are issues with fire pump room / mechanical room and no generator back up for fire pump. Group conference needed with appropriate people prior to continuing work in this part of project.
Electrical Rough-In2/9/20162/9/20162/9/2016PPASS
DetailsRex Boyles
Uffer inspections. Dave Johnson is the onsite contact. Phone #: ###-#### Inspection requested via web by Buster Bowen r/i ok
Electrical Rough-In2/2/20162/2/20162/2/2016PPASS
DetailsRex Boyles
Dave. Underground. Phone #: ###-#### Inspection requested via web by Sean DeLacy r/i u.ground from termination cab. over to stub up area ok