Final | 4/12/2016 | 4/12/2016 | 4/12/2016 | P | PASS |
Rock A. Hudson
|
|
|
Phone #: ###-#### Inspection requested via web by Thomas Jenkins Final ok
|
Final | 4/11/2016 | 4/12/2016 | 4/12/2016 | A | FAIL |
Rock A. Hudson
|
|
|
Thank you Phone #: ###-#### Inspection requested via web by Thomas Jenkins 110.16- Arc flash stickers on new disconnecting means. 210.64- A receptacle outlet shall be located within 50' of new service. 210.70- Rooms containing electrical equipment shall have luminaire installed. 300.15- In ele rm conductors hanging out of conduit shall terminate in a box. 330.30- Mezz. MC shall be secured within 12" of box. SL at switch. 422.51- Vending machine shall have GFCI protection.
|
Electrical Rough-In | 3/16/2016 | 3/17/2016 | 3/17/2016 | A | PASS |
Daryl DeGrange
|
|
|
Phone #: ###-#### Inspection requested via web by Thomas Jenkins rough-in ok cover underground to sign
|
Electrical Rough-In | 3/16/2016 | 3/16/2016 | 3/16/2016 | P | FAIL |
Rock A. Hudson
|
|
|
Underground for sign. Phone #: ###-#### Inspection requested via web by Thomas Jenkins Verbal with on site wireman. 300.5- Minimum depth of under roadway 24". 18 to 20 at time of inspection.
|
Electrical Rough-In | 3/11/2016 | 3/11/2016 | 3/11/2016 | P | CANC |
Rock A. Hudson
|
|
|
Inspection for underground conduit Phone #: ###-#### >> Inspection requested via web by Thomas Jenkins Inspection cancelled from web by: Thomas Jenkins
|
Electrical Rough-In | 2/22/2016 | 2/23/2016 | 2/23/2016 | A | PASS |
Rock A. Hudson
|
|
|
Need wall and ceiling inspection in the two large gym areas. Please feel free to contact me with any questions. Thank you Phone #: ###-#### Inspection requested via web by Thomas Jenkins Gym and storage areas walls and hard lids rough in ok cover
|
Electrical Rough-In | 2/4/2016 | 2/5/2016 | 2/5/2016 | A | PASS |
Rock A. Hudson
|
|
|
Phone #: ###-#### Inspection requested via web by Thomas Jenkins Bath and locker rooms rough in ok cover
|
Permanent Service | 1/25/2016 | 1/25/2016 | 1/25/2016 | A | PASS |
Rock A. Hudson
|
|
|
Re-inspect gear Phone #: ###-#### Inspection requested via web by Thomas Jenkins p/s o/h rec ok
|
Electrical Rough-In | 1/25/2016 | 1/25/2016 | 1/25/2016 | P | PASS |
Rock A. Hudson
|
|
|
Re-inspect gear Phone #: ###-#### Inspection requested via web by Thomas Jenkins Walls and hard lids in front offices, locker room not ready, main floor as noted on print. Rough in ok cover
|
Permanent Service | 1/21/2016 | 1/22/2016 | 1/22/2016 | P | FAIL |
Rock A. Hudson
|
|
|
We need a service inspection for IPCO to reconnect service. Thank you, Dale Phone #: ###-#### Inspection requested via web by Thomas Jenkins 110.22- Each disconnecting means shall be identified as to its purpose. 110.24- Available fault current chall be posted with date calculated prior to permanent service inspection. 250.90- Standard lock nuts and bushings shall not be only means of bonding service enclosures. bonding bushings required at all nipples. 300.4- Replace all bushings that are missing or damaged. 230.71- Max number of disconnecting means shall not exceed 6. Drawing shows total load of 301 amp plus well at 40 amps on 500 KCMIL service entrance rated at 380 amps 75 degrees.
|