Permit Information
Permit NumberELE15-04130
StatusFinaled
Name VANZANDT ELECTRIC
Site Address 6507 W RANDOLPH DR
Project Name 
Customer Number 
ePlanReviewNo
Description
Alteration or Repair: Rewire kitchen,bathroom
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final3/7/20163/7/20163/7/2016PPASS
DetailsRex Boyles
Phone #: ###-#### Inspection requested via web by John VanZandt corrections made final ok
Final3/1/20163/2/20163/2/2016AFAIL
DetailsRock A. Hudson
Phone #: ###-#### Inspection requested via web by John VanZandt
210.8- All bathroom receptacle outlets shall have GFCI protection. Stool.
210.52(C)(5) ex- Peninsular counter receptacle outlet shall not be located more than 6" back from edge of over hang.
406.4(D)(2)- Grounded type receptacle outlets installed on ungrounded circuit shall have GFCI protection or be changed to ungrounded type receptacle.
408.4- Circuit directory shall be completed.
Electrical Rough-In12/30/201512/30/201512/30/2015APASS
DetailsRock A. Hudson
Phone #: ###-#### Inspection requested via web by John VanZandt Kitchen and M. bath rough in ok cover