Final | 4/24/2016 | 4/25/2016 | 4/25/2016 | P | PASS |
Rock A. Hudson
|
|
|
Phone #: ###-#### Inspection requested via web by Neal Rumsey Final ok
|
Final | 4/14/2016 | 4/15/2016 | 4/15/2016 | P | FAIL |
Rock A. Hudson
|
|
|
call if you need the code Phone #: ###-#### Inspection requested via web by Neal Rumsey 210.8- Christmas GFCI shall be located in a readily accessible location. Below 6'7". 210.8(A)(2)- All 15 or 20 amp 120 volt receptacle outlets shall have GFCI protection. Opener outlet. 404.8- Switch used as disconnect for furnace shall be located under 6'7". Back patio light not working.
|
Rough-In Permanent Service | 1/12/2016 | 1/13/2016 | 1/13/2016 | P | PASS |
Eric Story
|
|
|
Phone #: ###-#### Inspection requested via web by Neal Rumsey corrections fixed rough-in ok cover p/s o/h n ok
|
Rough-In Permanent Service | 1/12/2016 | 1/12/2016 | 1/12/2016 | P | FAIL |
Rock A. Hudson
|
|
|
Phone #: ###-#### Inspection requested via web by Neal Rumsey 210.52(A)(2)1- Walls 2' or wider shall have a receptacle outlet install to serve wall space. 250.134- Metal box in net panel shall be connected to equipment grounding conductor. 300.4- In garage gronding electrode conductor wher ran through bored holes that do not maintain 1 1/4" from framing surface shall be protected from physical damage by nail plates. 300.4(G)- Raceways or connectors containing #4 or larger conductors shall have a bushing installed to protect wiring. 352.48- All joints between conduit bodies shall be done by an approved method. Garage LB to junction box. Glue BA to LB.
|
Rough-In Permanent Service | 1/11/2016 | 1/11/2016 | 1/11/2016 | A | NR |
Bob Reichert
|
|
|
Phone #: ###-#### Inspection requested via web by Neal Rumsey called electrical contractor, told him BLD description doesn't match street address, no address or job id posted, no esc signs posted, no u/g seen, ground wire cut at liberty service, shall protect nm cable within 6' of attic access, shall move outside boxes forward to be flush with finished surface on outsides of building, shall provide receptacles in 2' wall space, shall protect nm cable with nailplates, shall meet osha safety rules in liberty side with barrier at top of stairs and hall, shall establish grounding electrode for post side of structure, shall provide service riser straps within 3' of panel, add guy kit terminations
|