Information based on query as of Thursday, July 4, 2024.
Permit Information
Permit NumberELE16-00152
StatusFinaled
Name SUPERIOR ELECTRICAL CONTRACTORS
Site Address 108 S 11TH ST
Project Name 
Customer Number 
ePlanReviewNo
Description
New: New electrical for bar
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final3/10/20163/11/20163/11/2016APASS
DetailsDaryl DeGrange
Code 234 Phone #: ###-#### Inspection requested via web by Chris Chesnut correction done, final ok
Final3/10/20163/10/20163/10/2016PFAIL
DetailsEric Story
Code 234 Phone #: ###-#### Inspection requested via web by Chris Chesnut corrections not fixed (receptacle under shelves non GFCI protected and reverse polarity)
Final3/10/20163/10/20163/10/2016AFAIL
DetailsDaryl DeGrange
Door code 234 Phone #: ###-#### Inspection requested via web by Chris Chesnut Not all corrections have been completed.
Final3/8/20163/9/20163/9/2016AFAIL
DetailsRex Boyles
Door code 234 Phone #: ###-#### Inspection requested via web by Chris Chesnut 210.8(B)(7)- receptacles within 6 foot of sink shall have GFCI protection (back wall of bar), 110.16-Arc flash warning label on loadcenters, caulk walk in penetrations, old AC cable put in box or cut off.
Final3/4/20163/4/20163/4/2016PCANC
DetailsRex Boyles
Key code 234 Phone #: ###-#### >> Inspection requested via web by Chris Chesnut Inspection cancelled from web by: Chris Chesnut
Electrical Rough-In1/20/20161/21/20161/21/2016APASS
DetailsRex Boyles
234 key box code Phone #: ###-#### Inspection requested via web by Chris Chesnut r/i walls and ceiling ok
Conference1/18/20161/19/20161/19/2016ADONE
DetailsRex Boyles
Phone #: ###-#### Inspection requested via web by Chris Chesnut discuss mc cable use and ber receptacles requiring GFCI protection , exit and egress lighting and bathroom GFCI protected receptacles.