Final | 1/25/2017 | 1/25/2017 | 1/25/2017 | P | PASS |
Mark Moncarr
|
|
|
Christina Phone #: ###-#### Talked with Doug. Powerhouse is going to pull new permit for 2 light poles and signs so they can final out clubhouse and so they can get a C of O
|
Electrical Rough-In | 8/18/2016 | 8/18/2016 | 8/18/2016 | P | PASS |
James Ady
|
|
|
(2) Pole lights and entry signs linked to clubhouse Phone #: ###-#### Inspection requested via web by Bob Stephens Underground to light poles and column signs ok to cover. Pole base grounding ok
|
Final | 6/14/2016 | 6/15/2016 | 6/15/2016 | A | PASS |
Daryl DeGrange
|
|
|
Final - reinspection Phone #: ###-#### Inspection requested via web by Bob Stephens correction done, final ok
|
Final | 6/13/2016 | 6/14/2016 | 6/14/2016 | P | FAIL |
Daryl DeGrange
|
|
|
Doug Phone #: ###-#### NEC 210.8(B)(2) All 15 and 20 ampere 120 volt receptacle within 6ft of a sink requires GCFI protection. NEC 406.8(9)(B)(1) Receptacles installed in wet locations shall be listed weather-resistant type.NEC 406.12 Child care facilities require tamper-resistant receptacles. NEC 422.52 Electric drinking fountains require GFCI protection
|
Permanent Service | 6/7/2016 | 6/8/2016 | 6/8/2016 | A | PASS |
James Ady
|
|
|
Doug Phone #: ###-#### p/s u/g n ok
|
Electrical Rough-In | 2/10/2016 | 2/11/2016 | 2/11/2016 | A | PASS |
Eric Story
|
|
|
Re inspect rough electrical on clubhouse Phone #: ###-#### Inspection requested via web by Bob Stephens clubhouse ok cover(electrical room not ready at this point will call for another inspection on later date)
|
Electrical Rough-In | 2/9/2016 | 2/10/2016 | 2/10/2016 | P | NR |
Eric Story
|
|
|
Completion of Rough Electrical on the Club house Phone #: ###-#### Inspection requested via web by Bob Stephens still need securing of nm cable and emt not ready
|
Electrical Rough-In | 11/16/2015 | 11/17/2015 | 11/17/2015 | A | PASS |
Rock A. Hudson
|
|
|
Inspect pipe and floor plug boxes underground clubhouse-exercise room Phone #: ###-#### Inspection requested via web by Bob Stephens West area 4 floor boxes and conuit feeding them rough in ok cover
|