Description
Alteration: Provide the electrical installation for the Buffalo Wild Wings tenant improvement project including lighting, power and HVAC and fire alarm.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final8/8/20168/9/20168/9/2016APASS
DetailsEric Story
Please provide a final inspection at the Buffalo Wild Wings TI. Rod with Steed Construction should be on site and will be your contact there. His number is ###-####. Phone #: ###-#### Inspection requested via web by Kevin Perez
as per rock hudson all other areas were fine. correction fixed, installed GFCI breakers for bar area. final ok.
Final7/13/20167/13/20167/13/2016PFAIL
DetailsRock A. Hudson
Ben Phone #: ###-####
210.8- Receptacles located with in 6' of a sink shall have GFCI protection. Bar area and near water heater.
Critical systems related to core and shall be operational prior to final.
Electrical Rough-In7/6/20167/7/20167/7/2016APASS
DetailsDaryl DeGrange
Ceiling; Zach Phone #: ###-#### rough-in ok cover kitchen ceiling grid
Conference6/27/20166/27/20166/27/2016PDONE
DetailsRock A. Hudson
Ben Phone #: ###-####
Discussed transformer location above gear 1/2 in and out of grid. Wire rack for storage to be removed to the wid of transformer to provide required work space as per 110.26. With grid 2" in front of transformer cover is removable according to Ben. With gear over 800 amps door to left within 25' shall have panic hardware installed.
Conference5/5/20165/5/20165/5/2016PDONE
DetailsRex Boyles
Ben Phone #: ###-#### discuss transformer mounted halfway in and half way out of hardlid ceiling, also 480 volt conductors passing thru 208 volt section to get to x-former, also using 3 pole breakers for single phase branch circuits. Will get back to Ben asap
Electrical Rough-In4/21/20164/22/20164/22/2016PPASS
DetailsRex Boyles
Kevin Phone #: ###-#### r/i ok 100% on walls, showwindows, (including pony walls)and bath ceilings also ok
Conference4/13/20164/14/20164/14/2016ADONE
DetailsRex Boyles
Ben Phone #: ###-#### discuss working clearances for HVAC VAV's asked TVR to attempt to relocate controller if possible, if not raise up to maintain as much clearance as possible above beverage station
Electrical Rough-In4/7/20164/8/20164/8/2016APASS
DetailsRex Boyles
Ben Phone #: ###-#### r/i walls ok see Arch. sheets highlighted areas
Conference3/22/20163/23/20163/23/2016PDONE
DetailsRex Boyles
Dan Phone #: ###-#### discuss 240.24 height requirements for Main disconnect . 240.24(A)-calls for 6' 7" maximum. Panelboard rough in can is as low as can be with 4" lip for wash down health dept. requirement. Can't meet code requirement. Told Ben we willlook into this more.