Permit Information
Permit NumberELE16-00991
StatusFinaled
Name CENTERLINE ELECTRIC
Site Address 405 S ORCHARD ST
Project Name 
Customer Number 
ePlanReviewNo
Description
Alteration: Office building
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final5/27/20165/27/20165/27/2016PPASS
DetailsRock A. Hudson
Corrections made. Final ok
Final5/26/20165/27/20165/27/2016AFAIL
DetailsRock A. Hudson
Call John Binfet for access ###-#### Phone #: ###-#### Inspection requested via web by jamie berg
210.8(B)- Receptcle outlet located within 6' of sink in old kitchen area shall have GFCI protection.
*Receptacle outlets in basement not working.
Final3/31/20163/31/20163/31/2016PCANC
DetailsRex Boyles
Phone #: ###-#### Inspection requested via web by jamie berg needed r/i
Electrical Rough-In3/31/20163/31/20163/31/2016PPASS
DetailsRex Boyles
Phone #: ###-#### Inspection requested via web by jamie berg corrections made r/i ok
Electrical Rough-In3/30/20163/31/20163/31/2016AFAIL
DetailsRex Boyles
Key located in mail box slot at front door Phone #: ###-#### Inspection requested via web by jamie berg 300.4(A)(1)- 11/4" required from bored holes to edge of stud. nailplates required. see list on correction notice