Information based on query as of Friday, June 28, 2024.
Permit Information
Permit NumberELE16-01283
StatusFinaled
Name POWERHOUSE ELECTRIC
Site Address 12048 W DUNHAM LN
Project Name 
Customer Number 
ePlanReviewNo
Description
Complete Installation (includes room count and per: new home
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final5/26/20165/27/20165/26/2016APASS
DetailsEric Story
Phone #: ###-#### Inspection requested via web by Darryn Coburn correction fixed final ok
Final5/26/20165/26/20165/26/2016PPASS
DetailsEric Story
###-####
Correction fixed final ok
Final5/25/20165/26/20165/26/2016ANH
DetailsRock A. Hudson
Phone #: ###-#### Inspection requested via web by Darryn Coburn
House locked no garage door key pad. called for key location left message.
Final5/25/20165/25/20165/25/2016PFAIL
DetailsEric Story
Phone #: ###-#### Inspection requested via web by Darryn Coburn
110.7 Wiring integrity kitchen lights in-op
406.5 Receptacles shall be rigidly mounted(recept in garage loose)
Rough-In Permanent Service4/25/20164/26/20164/26/2016APASS
DetailsBob Reichert
Phone #: ###-#### Inspection requested via web by Darryn Coburn corrections made, ri ok, p/s u/g n ok
Rough-In Permanent Service4/22/20164/25/20164/25/2016AFAIL
DetailsRock A. Hudson
Phone #: ###-#### Inspection requested via web by Darryn Coburn
250.28- Main bonding jumper shall be installed. Bonding screw.
300.4- NM cable shall be protected from physical damage where run thru bored holes that do not maintain 1 1/4" from framing surface. Above panel, dn west bed, up center bed.
330.30- Secure and support NM cable. Supports shall not exceed 4 1/2' above living window. Secure up master stool switch and secure NM cable within 12" of box.