Temporary Service | 5/5/2016 | 5/5/2016 | 5/5/2016 | A | PASS |
James Ady
|
|
|
Phone #: ###-#### Inspection requested via web by Brandon Winters T/S U/G N OK
|
Temporary Service | 5/3/2016 | 5/4/2016 | 5/4/2016 | A | FAIL |
Bob Reichert
|
|
|
Temporary power pole for ACHD pump control panel. Phone #: ###-#### Inspection requested via web by Brandon Winters called, left correction notice, NEC 406.9(B) receptacles shall be listed WR type and shall have in-use cover installed, 408.4 shall provide correct circuit directory, 110.12(A) shall close unused openings in panel, BCC shall post job id sticker, use listed equipment-ground lug
|