Information based on query as of Tuesday, July 16, 2024.
Permit Information
Permit NumberELE16-01410
StatusFinaled
Name WINTERS ELECTRIC LLC
Site Address 289 N ALTO VIA CT
Project Name 
Customer Number16-176
ePlanReviewNo
Description
Temporary Power Pole: Temporary power pole and pump/pump control panel for ACHD
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Temporary Service5/5/20165/5/20165/5/2016APASS
DetailsJames Ady
Phone #: ###-#### Inspection requested via web by Brandon Winters
T/S U/G N OK
Temporary Service5/3/20165/4/20165/4/2016AFAIL
DetailsBob Reichert
Temporary power pole for ACHD pump control panel. Phone #: ###-#### Inspection requested via web by Brandon Winters called, left correction notice, NEC 406.9(B) receptacles shall be listed WR type and shall have in-use cover installed, 408.4 shall provide correct circuit directory, 110.12(A) shall close unused openings in panel, BCC shall post job id sticker, use listed equipment-ground lug