Permit NumberELE16-01667
StatusFinaled
Name LEA ELECTRIC LLC
Site Address 611 S 8TH ST
Project NameThe Afton
Customer Number2015-13
ePlanReviewNo
Description
New: New electrical construction including conduit wire, wiring devices, panels, receptacles, fixtures, fire alarm, CCTV and TeleComm.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final9/6/20179/6/20179/6/2017PPASS
DetailsRock A. Hudson
Unit 203 , re-inspect planter recepts should be last final inspection, ready for sign off Call Craig Phone #: ###-#### Inspection requested via web by Tom Betty
Final ok
Final8/29/20178/30/20178/30/2017APART
DetailsEric Story
Units 210 , 202 Call Craig Phone #: ###-#### Inspection requested via web by Tom Betty
Units 210,202 ok to occupy
Final8/22/20178/22/20178/22/2017APART
DetailsRock A. Hudson
Unit 106 and Finish 105 Call Craig Phone #: ###-#### Inspection requested via web by Tom Betty
Rooms noted TCO ok
Final8/18/20178/21/20178/21/2017APART
DetailsRock A. Hudson
unit 105,107 Call Craig Phone #: ###-#### Inspection requested via web by Tom Betty 107 bath GFI in op and kitchen not complete. 105 TCO ok
Final8/10/20178/11/20178/11/2017APART
DetailsRock A. Hudson
Live works 103 and 104 Call Craig Phone #: ###-#### Inspection requested via web by Tom Betty
Rooms as noted on print but actual labels different. TCO ok
Electrical Rough-In6/26/20176/26/20176/26/2017PPASS
DetailsRock A. Hudson
Drop ceilings 211 , 212 Phone #: ###-#### Inspection requested via web by Tom Betty Areas noted rough in ok cover
Electrical Rough-In6/22/20176/22/20176/22/2017PPASS
DetailsMark Moncarr
Drop Ceilings Town house 111 , 112 , 113 , 213 Phone #: ###-#### Inspection requested via web by Tom Betty Ok cover bath ceilings and EVU's in rooms 111-113 and 213
Final6/21/20176/21/20176/21/2017PPART
DetailsRock A. Hudson
Unit 208 Phone #: ###-#### Inspection requested via web by Tom Betty
208 TCO ok
Final6/20/20176/20/20176/20/2017PPART
DetailsJames Ady
unit 305 studio , amenities , unit 208 Phone #: ###-#### Inspection requested via web by Tom Betty 208 not ready. 305 , Amenities ok. Corrections made 204,203 and 602.
Final6/19/20176/19/20176/19/2017PPART
DetailsRock A. Hudson
Final inspections for units #203 and #204 and Studio #305.
Contact Craig Timmons
Thank you Phone #: ###-#### Inspection requested via web by Cathy Duchek
305 not ready, mini split fusing ok, heater covers installed, 2nd elevator lobby receptacles ok, 603 owner wanted walk in tub with out electrical hooked up, 203, 204, 603 only TCO ok
Final6/16/20176/16/20176/16/2017PPART
DetailsRock A. Hudson
Afton Contact Craig Timmons ###-####
Finals on Stairway #3
Lobbies on the 1st and 2nd floors
Units 601,602,603, and 604
All Trash rooms.

Thank you. Phone #: ###-#### Inspection requested via web by Cathy Duchek
Mini-split smaller units fusing 20 max, out receptacle on motion sensor com rm, planter receptacles locate out of soil,
Heat trace not in, EPD breakers installed,
Heater covers to install in trash rooms 3-6,
Check elevator lobby receptacles, off,
603 GFCI protection for walk in tub,
602 Island receptacles need installed.
Not completed- Live/works office areas to remain vanilla space, Live works appartments 203, 204, 208.
Town house units 111, 112, 113, 211, 212, 213. Elevators not complete.
Completed- Out egress, Stair 1,2,3, Garages 1,2, Corridors 3,4,5,6, 301 thru 304, 401 thru 405, 501 thru 505, 601,604,605, lobby 1,2.
TCO for areas noted complete.
Final6/15/20176/15/20176/15/2017PNR
DetailsRock A. Hudson
Units 503 , 504 , 505 , 605 , Roof Phone #: ###-#### Inspection requested via web by Tom Betty
Out receptacle roof com room switched by photo cell, Fuse smaller HVAC units to 20 amp noted on name plate, all outdoor receptacles on roof shall have in-use covers.
Rooms noted checked OK.
Final6/14/20176/14/20176/14/2017PNR
DetailsRock A. Hudson
Re-inspect 401 and inspect 501 , 502 Corridor 3rd , 4th , 5th , 6th , Garage 1st 2nd and stairs #1 , #2 Phone #: ###-#### Inspection requested via web by Tom Betty
Checked 401, 501, 502, level 1 trash rm, level 2 storage rm, bike rm OK, Corridors duplex receptacles shall be WR as per 406, Planter receptacles shall not be in soil, Check flexible cord on garage door opener, stair 3 NR, lobbies NR
Final6/12/20176/13/20176/13/2017APEND
DetailsRock A. Hudson
Re-inspect 301 , 302 , 303 ,304 , 402 , 403 , 404 and finals on 401 , 405 Phone #: ###-#### Inspection requested via web by Tom Betty
401 had receptacles not working in family, and halls. 301 thru 304 and 402 thru 405 checked out OK. TCO pending stairways, out egress, core and shell areas approval
Final6/8/20176/8/20176/8/2017AFAIL
DetailsRock A. Hudson
Just units 301,302,303,304,402,403,404 Call Craig Phone #: ###-#### Inspection requested via web by Tom Betty
4-05-24 Inspection required on all floor heat installions.
210.52(B)- Kitchen counter top areas shall have a receptacle outlet with 24" of edge of counter. counter off dining area 1 receptacle on left of 48" counter top.
250.140- Dryers in units shall have grounded and grounding terminations seperated. In cord junction 2 white grounded present, 1 terminated with neutral and 1 with ground.
410.16(C)- Closet luminaires, for recessed 6" minimum clearance from storage shelf, for surface LED 12" clearance required. Several unit too close.
422.11(A)- Water heaters shall be fused to manufacturers specs. 60 amp installed on 25 amp recommended fusing.
422.30- A disconnecting means shall be provided to disconnect ungrounded from appliances. Water heaters and range hoods.
Unit 403 deck receptacle not trimmed.
Electrical Rough-In5/9/20175/9/20175/9/2017PPASS
DetailsMark Moncarr
About 100 feet of trench Call Craig Phone #: ###-#### Inspection requested via web by Tom Betty Ok cover. 2 runs of 1" to 2 pole lights on S side of building.
Electrical Rough-In5/2/20175/3/20175/3/2017APASS
DetailsRock A. Hudson
Garden Shed and drop ceiling 305 Suite and 307 amenities Phone #: ###-#### Inspection requested via web by Tom Betty
Garden shed wiring must be covered prior to weater. Rough in ok cover
Electrical Rough-In4/11/20174/11/20174/11/2017APASS
DetailsRock A. Hudson
Inspect drop ceiling and reinspect fire pump service Call Craig Phone #: ###-#### Inspection requested via web by Tom Betty East soffit cans and lobby grid rough in ok cover
Permanent Service4/11/20174/11/20174/11/2017PPASS
DetailsRock A. Hudson
Inspect drop ceiling and reinspect fire pump service Call Craig Phone #: ###-#### Inspection requested via web by Tom Betty Fire pump p/s u/g n ok
Permanent Service3/13/20173/13/20173/13/2017PFAIL
DetailsRock A. Hudson
Firepump service.
695.4- Overcurrent device shall carry indefinately locked rotor current. 400 installed 500 amp min. Contractor to change to 600 amp knife switch.
695.6- Wiring method to jockey pump shall be one listed, standard MC cable not listed.
Permanent Service3/10/20173/13/20173/13/2017APASS
DetailsRock A. Hudson
Call Craig Phone #: ###-#### Inspection requested via web by Tom Betty
Fire pump service not included.
30 single phase meters, 2 3 phase meters. p/s u/g n ok
Electrical Rough-In3/1/20173/2/20173/2/2017APASS
DetailsRock A. Hudson
Town house 112 and 1st and 2nd floor lobby Call Craig Phone #: ###-#### Inspection requested via web by Tom Betty
Areas noted walls and hardlids rough in ok cover
Electrical Rough-In2/21/20172/22/20172/22/2017APASS
DetailsEric Story
Drop ceilings 602,603,and 604 Call Craig Phone #: ###-#### Inspection requested via web by Tom Betty
Ceiliings in units 602,603,604 hard lids ok cover
Electrical Rough-In2/20/20172/21/20172/21/2017APART
DetailsRock A. Hudson
Drop ceiling 601,602,603,604,605,bike room area and comm room on roof call Craig Phone #: ###-#### Inspection requested via web by Tom Betty
103, 104, 109 walls and hardlids, 601, 605 only drop ceilings, bike rm, 1,2 storage rms, comm room roof rough in ok cover
Electrical Rough-In2/16/20172/16/20172/16/2017APASS
DetailsRock A. Hudson
Town house 211,212,213 Call Craig Phone #: ###-#### Inspection requested via web by Tom Betty
Check for lights in storage rooms. Areas noted rough in ok cover
Electrical Rough-In1/30/20171/30/20171/30/2017APASS
DetailsRock A. Hudson
Reinspect storage walls and stairwell #3 Call Craig Phone #: ###-#### Inspection requested via web by Tom Betty
Storage rm and corridor, and stair 3 walls 2nd floor rough in ok cover
Electrical Rough-In1/25/20171/26/20171/26/2017APART
DetailsRock A. Hudson
Storage room , comm room and some entry room walls Call Craig Phone #: ###-#### Inspection requested via web by Tom Betty
2nd floor corridor to storage remove drywall that was installed prior to inspection.
2nd floor areas noted rough in ok cover
Electrical Rough-In1/18/20171/19/20171/19/2017APASS
DetailsRock A. Hudson
Drop ceiling room 208 and some walls in entry call Craig Phone #: ###-#### Inspection requested via web by Tom Betty
208 and hall off pet wash and stair 1 side rough in ok cover
Electrical Rough-In1/5/20171/6/20171/6/2017APASS
DetailsRock A. Hudson
Three drop ceilings call craig Phone #: ###-#### Inspection requested via web by Tom Betty

503, 504, 505 drop ceiling rough in ok cover
Electrical Rough-In12/14/201612/14/201612/14/2016APASS
DetailsRock A. Hudson
Some drop ceilings and couple walls call craig Phone #: ###-#### Inspection requested via web by Tom Betty
112 ADA not ready check panel height.
111, 113 town houses, 203, 204, 405, 501, 502 drop lids, 504, 504 firewall rough in ok cover
Electrical Rough-In11/29/201611/30/201611/30/2016APASS
DetailsRock A. Hudson
Four drop ceilings Call Craig Phone #: ###-#### Inspection requested via web by Tom Betty
Units 401, 402, 403, 404 drop ceilings rough in ok cover
Electrical Rough-In11/17/201611/18/201611/18/2016APASS
DetailsEric Story
Inspect 3rd floor stair landing in stairwell 1 and 2 call Craig Phone #: ###-#### Inspection requested via web by Tom Betty
stair 1@2 protection of MC ok
Electrical Rough-In11/16/201611/17/201611/17/2016APASS
DetailsEric Story
Stairs and corridors.Call Craig Phone #: ###-#### Inspection requested via web by Tom Betty
Stairs 1@2,trash rooms,corridors,data room,storage ok cover. EC will call another rough-in in for MC wrapped around metal beams, will install in a raceway to protect from physical damage. Inspection will .be 11-18-16
Electrical Rough-In10/24/201610/25/201610/25/2016APASS
DetailsRock A. Hudson
Unit 601 and one wall Call Craig Phone #: ###-#### Inspection requested via web by Tom Betty
Unit 601 and firewall in 304 rough in ok cover
Electrical Rough-In10/7/201610/14/201610/14/2016PPASS
DetailsRock A. Hudson
Four units will be ready Call Craig Phone #: ###-#### Inspection requested via web by Tom Betty
Units 208, 602, 603, 604, 605, firewalls to be done in future. walls and hardlids rough in ok cover
Electrical Rough-In10/6/201610/6/201610/6/2016APASS
DetailsRock A. Hudson
One unit ready Call Craig Phone #: ###-#### Inspection requested via web by Tom Betty
Unit 203 only walls only rough in ok cover
Electrical Rough-In9/27/20169/28/20169/28/2016PPASS
DetailsEric Story
Need 4 to 5 units Call Craig Phone #: ###-#### Inspection requested via web by Tom Betty
room 240 and 5th floor rooms walls only ok cover (wall with house panels will need to be looked at once complete)
Conference9/21/20169/21/20169/21/2016PDONE
DetailsMark Moncarr
Had talked to Rock about access to split system heating above hard lid with access door.Need some clarification on working accessibility. Phone #: ###-#### Inspection requested via web by Tom Betty Manufacturers specs call for minimum 18" of working clearance for access panel.
Electrical Rough-In9/13/20169/14/20169/14/2016APASS
DetailsEric Story
Four to Five units ready , Craig Phone #: ###-#### Inspection requested via web by Tom Betty
304(exept west wall,once furred out will need to looked at)3rd floor ammendities and suite (exept east and north wall) 403,404 (except west wall) 405 ok cover
Electrical Rough-In9/2/20169/6/20169/6/2016PPASS
DetailsMark Moncarr
Will have 4 to 5 units ready.call Craig Phone #: ###-#### Inspection requested via web by Tom Betty ok to cover rms 301, 302, 303, 401, 402
Conference7/14/20167/15/20167/15/2016APASS
DetailsRock A. Hudson
Discuss use of romex in all condo''s with Craig Phone #: ###-#### Inspection requested via web by Tom Betty
Discussed use of NM cable in condos. Building permit noted type V construction. NM cable shall have at least 15 minute fire barrier and not be installed above drop or grid ceilings as per NEC 334.10. Also mentioned access to HVAC unit control boxes shall have room to access.