Final | 7/28/2017 | 7/28/2017 | 7/28/2017 | P | PART |
James Ady
|
|
|
Lower clubhouse and corrections on appartment level Phone #: ###-#### Inspection requested via web by Harley Woodward GFCI protect drinking fountain, hood wire, Spark ring kitchen, RCR50 on transformer cord in com room Blanks on 4sq in fire riser room and 2 Single gang next to house panels.
|
Final | 7/28/2017 | 7/28/2017 | 7/28/2017 | P | PASS |
James Ady
|
|
|
Lower clubhouse and corrections on appartment level Phone #: ###-#### Inspection requested via web by Harley Woodward Corrections made Final ok
|
Electrical Rough-In | 7/12/2017 | 7/12/2017 | 7/12/2017 | P | PASS |
James Ady
|
|
|
Pool steel bonding connections for equipotental loop Phone #: ###-#### Inspection requested via web by Harley Woodward Corner bonding only ok to cover
|
Final | 7/6/2017 | 7/7/2017 | 7/7/2017 | A | NR |
James Ady
|
|
|
Ken Phone #: ###-#### not ready
|
Final | 7/6/2017 | 7/6/2017 | 7/6/2017 | P | FAIL |
James Ady
|
|
|
Chris Phone #: ###-#### Job General calling in inspections for Sub contractors. Job Not ready for final.
|
Permanent Service | 6/8/2017 | 6/8/2017 | 6/8/2017 | P | PASS |
James Ady
|
|
|
Power to panel for clubhouse meter cluster Phone #: ###-#### Inspection requested via web by Harley Woodward p/s u/g n ok 8 meters
|
Electrical Rough-In | 6/1/2017 | 6/2/2017 | 6/2/2017 | A | PASS |
James Ady
|
|
|
Club house loby ceilings rough electrical Phone #: ###-#### Inspection requested via web by Harley Woodward Ceiling only ok to cover
|
Electrical Rough-In | 5/30/2017 | 5/31/2017 | 5/31/2017 | P | PASS |
James Ady
|
|
|
Above metal frame cielings inspection for rough electrical Phone #: ###-#### Inspection requested via web by Harley Woodward rough in ceiling only ok cover
|
Electrical Rough-In | 5/15/2017 | 5/16/2017 | 5/16/2017 | A | PASS |
James Ady
|
|
|
Am if possible. Just bathroom cielings in lower clubhouse level. Thanks. Phone #: ###-#### Inspection requested via web by Harley Woodward Bathrooms only Ceiling only ok to cover
|
Electrical Rough-In | 5/9/2017 | 5/10/2017 | 5/10/2017 | A | PASS |
James Ady
|
|
|
Apartments above clubhouse, light boxes in metal framed cielings. 6 units. Phone #: ###-#### Inspection requested via web by Harley Woodward 6 apartments, Laundry room ceiling only ok to cover
|
Electrical Rough-In | 4/27/2017 | 4/27/2017 | 4/27/2017 | P | PASS |
James Ady
|
|
|
Stairwell rough electrical Phone #: ###-#### Inspection requested via web by Harley Woodward Stair well ok to cover
|
Electrical Rough-In | 4/12/2017 | 4/12/2017 | 4/13/2017 | P | PASS |
James Ady
|
|
|
Morgan Phone #: ###-#### NW half 3rd floor ok to cover
|
Electrical Rough-In | 4/6/2017 | 4/7/2017 | 4/7/2017 | P | FAIL |
James Ady
|
|
|
Main floor club house electrical rough in, excluding yoga studio ceiling, wall mounted meter section and adjacent room, and stairwells. ( sorry- superintendent pushing to insulate as much as possible) Phone #: ###-#### Inspection requested via web by Harley Woodward Too many items unfinished, multiple nail plates, unstuffed boxes,
|
Electrical Rough-In | 4/6/2017 | 4/6/2017 | 4/6/2017 | P | PART |
James Ady
|
|
|
Chris-3 walls on main floor Phone #: ###-#### ok to cover
|
Electrical Rough-In | 3/9/2017 | 3/10/2017 | 3/10/2017 | A | PASS |
James Ady
|
|
|
1-6; chris Phone #: ###-#### 2nd floor only Rough in ok
|
Electrical Rough-In | 10/5/2016 | 10/6/2016 | 10/6/2016 | A | PASS |
Rock A. Hudson
|
|
|
Alex Phone #: ###-#### Reinspect pole base damaged and redone. South east pole base. Rough in ok cover
|
Electrical Rough-In | 8/30/2016 | 8/31/2016 | 8/31/2016 | A | PASS |
Bob Reichert
|
|
|
Alex-unbderground for pole lights Phone #: ###-#### ok u/g for site lighting less 1 pole base to be re-inspected
|