Final | 2/3/2017 | 2/3/2017 | 2/3/2017 | A | PASS |
James Ady
|
|
|
Code 2010 Phone #: ###-#### Inspection requested via web by Jason Wicks final ok
|
Final | 1/31/2017 | 1/31/2017 | 1/31/2017 | P | FAIL |
James Ady
|
|
|
Code 2010 Phone #: ###-#### Inspection requested via web by Jason Wicks 210.52.C 1 Recep shall be installed within 24in of cook top 230.70. Each structure shall have disc. mean ( Detached garage) 314.20 Boxes set back more than1/4in shall have extension rings. (all weather proof, mirrors and Up stair 2gang for wall sconce.) 422.30 Furnace shall have Disc means. 334.12 B4 NM cable shall not be installed in wet location 300.9 the inside of an above ground conduit shall be considered a wet location (NM cable going to A/C disconnect)
|
Rough-In Permanent Service | 10/12/2016 | 10/12/2016 | 10/12/2016 | P | PASS |
James Ady
|
|
|
Phone #: ###-#### Inspection requested via web by Jason Wicks rough in ok p/s u/g n ok
|