Permit Information
Permit NumberELE17-00037
StatusFinaled
Name LEA ELECTRIC LLC
Site Address 1401 S LUSK PL
Project Name 
Customer Number3618
ePlanReviewNo
Description
Alteration: Electrical demolition and installation in existing hotel units. Work includes removal of existing fixtures and receptacles and installation of updated light fixtures, wiring and recepts as needed.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final5/5/20175/8/20175/8/2017PPASS
DetailsRock A. Hudson
Final Inspection on ADA Units 811 and 813
Contact Dan Hutchinson
Thank you Phone #: ###-#### Inspection requested via web by Cathy Duchek
All units done. Final ok
Final5/4/20175/5/20175/5/2017PPART
DetailsRock A. Hudson
Final inspection on building 7 and ADA unit 1013
Contact Dan Hutchinson
Thank you. Phone #: ###-#### Inspection requested via web by Cathy Duchek
BLDG and unit noted TCO OK
Final5/2/20175/3/20175/3/2017APART
DetailsRock A. Hudson
Final for Units 513 and 613
Contact Dan Hutchinson
Thank you Phone #: ###-#### Inspection requested via web by Cathy Duchek
Rooms noted TCO OK
Final5/2/20175/2/20175/2/2017PPART
DetailsRock A. Hudson
Final on Building 8 excluding 811 and 813.
Contact Dan Hutchinson Phone #: ###-#### Inspection requested via web by Cathy Duchek
Rooms noted not ready rest TCO OK
Final4/27/20174/28/20174/28/2017PPART
DetailsRock A. Hudson
Final on Building 8 and Final on Building 4 units 411 and 413.
Contact Dan Hutchinson
Thank you Phone #: ###-#### Inspection requested via web by Cathy Duchek
Building 8 some GFCI devices not tamper resistant. 406.12(B)- All 15 and 20 amp 120 volt receptacle outlets shall be tamper resistant type
411 and 413 only TCO ok
Electrical Rough-In4/24/20174/24/20174/24/2017PPASS
DetailsRock A. Hudson
Ceiling Rough in Inspection for Building 7
Contact Dan Hutchinson @ ###-#### or ###-####
Thank you. Phone #: ###-#### Inspection requested via web by Cathy Duchek
BLDG 7 all units rough in ok cover
Electrical Rough-In4/19/20174/20/20174/20/2017APASS
DetailsRock A. Hudson
Rough-In Inspection for units 811 ; 813
Contact Dan Hutchinson
Thank you. Phone #: ###-#### Inspection requested via web by Cathy Duchek
Area noted rough in ok cover
Final4/18/20174/19/20174/19/2017PPART
DetailsRock A. Hudson
Final Inspection for Building 14.
Contact Dan Hutchinson
Thank you. Phone #: ###-#### Inspection requested via web by Cathy Duchek
Junction box removed in 1411. TCO OK
Final4/14/20174/17/20174/17/2017PPART
DetailsRock A. Hudson
Final for Building 12
Contact Dan Hutchinson
Thank you. Phone #: ###-#### Inspection requested via web by Cathy Duchek
406.12 ex.2- Receptacles that are part of a luminare not required to be tamper resistant. Luminaire, swithes, and receptacles all mounted on back plate.
TCO building 12 ok
Final4/13/20174/14/20174/14/2017PFAIL
DetailsEric Story
Final Inspection for Building 12
Contact Dan Hutchinson
Thank you Phone #: ###-#### Inspection requested via web by Cathy Duchek
406 Tamper resistant required for all 120v receptacles
Electrical Rough-In4/13/20174/14/20174/14/2017PPASS
DetailsEric Story
Rough-In Inspection on Building 8
Contact Dan Hutchinson
Thank you Phone #: ###-#### Inspection requested via web by Cathy Duchek
Building 8 minus ADA rooms ok cover
Electrical Rough-In4/10/20174/10/20174/10/2017APASS
DetailsRock A. Hudson
Rough In Inspection on Building #14
Contact Dan Hutchinson
Thank you, Phone #: ###-#### Inspection requested via web by Cathy Duchek
Check on final 1411 junction box in ceiling in front of panel, ground splice out of box and wrong color. Rough in ok cover
Electrical Rough-In4/5/20174/6/20174/6/2017PPASS
DetailsRock A. Hudson
Rough in inspection for Building 12
Contact Dan Hutchinson
Thank you Phone #: ###-#### Inspection requested via web by Cathy Duchek
Rough in ok cover
Electrical Rough-In4/5/20174/5/20174/5/2017PCANC
DetailsRock A. Hudson
Rough-In inspection for Building 12
Contact Dan Hutchinson
Thank you Phone #: ###-#### >> Inspection requested via web by Cathy Duchek Inspection cancelled from web by: Cathy Duchek
Final4/4/20174/5/20174/5/2017APART
DetailsRock A. Hudson
Final Inspection on Building 11
Contact Dan Hutchinson
Thank you Phone #: ###-#### Inspection requested via web by Cathy Duchek
622, 623, bldg 11 TCO ok
Final3/29/20173/30/20173/30/2017APART
DetailsRock A. Hudson
Final Inspection for Building 10
Contact Dan Hutchinson
Thank you, Phone #: ###-#### Inspection requested via web by Cathy Duchek
1013 not ready, rest TCO ok
Electrical Rough-In3/29/20173/30/20173/30/2017APASS
DetailsRock A. Hudson
Rough In Inspection for unit #513
Contact Dan Hutchinson.
Thank you Phone #: ###-#### Inspection requested via web by Cathy Duchek
Room noted rough in ok cover
Electrical Rough-In3/27/20173/28/20173/28/2017APASS
DetailsRock A. Hudson
Rough-In Inspection for Handicap units 613 and 1013.
Contact Dan Hutchinson
Thank you, Phone #: ###-#### Inspection requested via web by Cathy Duchek
check fusing on bath receptacle 15 amp on final. Rooms noted rough in ok cover
Electrical Rough-In3/22/20173/23/20173/23/2017APASS
DetailsJames Ady
Final inspection for Building 9 and Rough-In inspection for Building 11
Contact Dan Hutchinson
Thank you. Phone #: ###-#### Inspection requested via web by Cathy Duchek Buildin 9 final ok. Building 11 Rough in ok, Units 622,623 Still need finaled. 613 Still needs Rough in.
Final3/16/20173/17/20173/17/2017AFAIL
DetailsRock A. Hudson
Final inspection for building 9 and final inspection for units 622, and 623.
Contact Dan Hutchinson Phone #: ###-#### Inspection requested via web by Cathy Duchek
622- Water heater lockout needed, 623- lockout on wrong breaker needed WH. Building 9 not ready DW missing and floor receptacles not trimmed.
Electrical Rough-In3/16/20173/16/20173/16/2017APASS
DetailsRock A. Hudson
Building 10 Rough-in inspection
Contact Dan Hutchinson
Thank you, Phone #: ###-#### Inspection requested via web by Cathy Duchek
1013 not ready, rest of bldg 10 rough in ok cover
Final3/10/20173/10/20173/10/2017PPART
DetailsJames Ady
Building #6 final
Contact Dan Hutchinson
Thank you Phone #: ###-#### Inspection requested via web by Cathy Duchek 613 not ready, 624 missing floorbox cover, 622 Up Bath GFCI and up bath lights in-op. Partial final on all other units ok
Electrical Rough-In3/9/20173/10/20173/10/2017PPASS
DetailsJames Ady
Rough-In Inspection for Building #9
Contact Dan Hutchinson
Thank you Phone #: ###-#### Inspection requested via web by Cathy Duchek Micro Recep and paddle fan add rough in ok
Final3/2/20173/3/20173/3/2017PPART
DetailsRock A. Hudson
Final Inspection for Building #5
Contact Dan Hutchinson
Thank you. Phone #: ###-#### Inspection requested via web by Cathy Duchek
513 excluded, rest of building 5 TCO ok.
Electrical Rough-In2/28/20173/1/20173/1/2017APART
DetailsRock A. Hudson
Rough-In Inspection on Building #6.
Contact Dan Hutchinson
Thank you Phone #: ###-#### Inspection requested via web by Cathy Duchek
613 not ready. Paddle fan boxes installed, splice kits used for bath fans listed and installed correctly. Rest of bldg 6 rough in ok cover
Final2/27/20172/27/20172/27/2017PPART
DetailsRock A. Hudson
Final Inspection for Building #4
Contact Dan Hutchinson
Thank you. Phone #: ###-#### Inspection requested via web by Cathy Duchek
411, 413 not ready... rest TCO ok
Final2/23/20172/24/20172/24/2017PFAIL
DetailsRock A. Hudson
Final Inspection for Six (6) non-ADA units in Building #5
Contact Dan Hutchinson
Thank you. Phone #: ###-#### Inspection requested via web by Cathy Duchek
Wrong building noted wanted BLDG #4.
Created rough in for 411 and 413.
422.30- Lockout for water heaters required in all units not within sight of panel. 300.15- Unit 422 missing cover plates.
Electrical Rough-In2/24/20172/24/20172/24/2017PPASS
DetailsRock A. Hudson
Final Inspection for Six (6) non-ADA units in Building #5
Contact Dan Hutchinson
Thank you. Phone #: ###-#### Inspection requested via web by Cathy Duchek
Units 411, 413 not to be advertised as ADA units so not required to be ADA compliant. Units noted rough in ok cover
Electrical Rough-In2/21/20172/22/20172/22/2017PPART
DetailsRock A. Hudson
Rough-in Inspection for Residence Inn Building #5
Contact Dan Hutchinson
Thank you Phone #: ###-#### Inspection requested via web by Cathy Duchek
ADA unit not ready, paddle fan wiring and box install not done, bath fan change out not done. Bath fans and paddle fans OK to complete with out inspections.
All but ADA unit rough in ok cover
Electrical Rough-In2/15/20172/16/20172/16/2017APASS
DetailsRock A. Hudson
Rough-In Building #4
Contact Dan Hutchinson
Thank you. Phone #: ###-#### Inspection requested via web by Cathy Duchek
Building 4 except units 411, 413 ADA units. J-box above panel due to damaged wire in 433. Fans done. Others rough in ok cover
Final2/14/20172/14/20172/14/2017PPART
DetailsRock A. Hudson
Final Inspection for Building #3
Contact Cesar Salcedo Phone #: ###-#### Inspection requested via web by Cathy Duchek Building #3 TCO OK
Final2/8/20172/9/20172/9/2017APART
DetailsRock A. Hudson
Final Inspection for Building #2
Contact Cesar Salcedo
Thank you Phone #: ###-#### Inspection requested via web by Cathy Duchek
TCO building #2 temp final ok
Final2/3/20172/3/20172/3/2017PPART
DetailsRock A. Hudson
Final Inspection for Building #1
Contact Cesar Salcedo
Thank you Phone #: ###-#### Inspection requested via web by Cathy Duchek
TCO for building 1 ok
Final1/31/20172/3/20172/3/2017AFAIL
DetailsRock A. Hudson
Final Inspection for Building #1
AM Inspection preferred
Contact Cesar Salcedo
Thank you Phone #: ###-#### Inspection requested via web by Cathy Duchek
210.8- All 15 or 20 amp receptacle outlets located within 6' of a sink shall have GFCI protection. All units.
406.12- All 15 and 20 amp receptacle outlets shall be tamper resistant type. Receptacle built into stair light. 124.
422.30- A means shall be provided to disconnect water heater power shall be within sight of unit. 110.25- lockout acceptable.
Conference2/1/20172/2/20172/2/2017ADONE
DetailsRock A. Hudson
Consultation for Building #1
Contact Cesar Salcedo.
Thank you. Phone #: ###-#### Inspection requested via web by Cathy Duchek
Contractor wanted to check for approval on receptacle outlets each side of bed. The units are guest rooms.
As per 210.60(B)- receptacles shall be located so attachment plug will not be in contact with bed furniture. They will install a junction box behind removeable headboard and move receptacle where needed.
Final1/26/20171/27/20171/27/2017PCANC
DetailsEric Story
Check ceilng fan boxes on bld 2@3
NO final just Rough-in
Electrical Rough-In1/27/20171/27/20171/27/2017PPASS
DetailsEric Story
Check ceilng fan boxes on bld 2@3
Verified u/l listing fan boxes being used to support paddle fans
Electrical Rough-In1/25/20171/26/20171/26/2017APASS
DetailsEric Story
Building 3 Rough-In
Contact Cesar Salcedo
Thank you, Phone #: ###-#### Inspection requested via web by Cathy Duchek
Building 3 circuits added for micro ok cover
Electrical Rough-In1/20/20171/23/20171/23/2017APASS
DetailsEric Story
Rough-In Wall Inspection Building 2
Contact Cesar Salcedo
###-#### Phone #: ###-#### Inspection requested via web by Cathy Duchek
Issue with paddel fan without boxes and non compliant wiring with be resolved with proper methods. Building 2 addition for micro ok cover
Electrical Rough-In1/11/20171/18/20171/18/2017ADONE
DetailsRock A. Hudson
Tom ###-#### Check temp wiring on club house to sign.
Temp wiring has been removed. Thank You
Electrical Rough-In1/13/20171/17/20171/17/2017APASS
DetailsRock A. Hudson
Rough-in Inspection.
Contact Cesar Salcedo
Thank you Phone #: ###-#### Inspection requested via web by Cathy Duchek
Temp power issue on ELE16-04108 gate house.
To still check paddle fan boxes on 2nd floor. Addition of microwave circuit on all 8 units for building 1 rough in ok cover
Conference1/9/20171/11/20171/12/2017ADONE
DetailsRock A. Hudson
Consult about new code requirements in old building. Contact Tom Betty. Phone #: ###-#### Inspection requested via web by Cathy Duchek
Discussed electrical requirements of remodel. Walls will not have drywall removed will be repainted. Patches will be created to add microwave circuits. Surface mounted conduits shall be listed assembly, receptacles shall be tamper resistant type, range receptacles shall be 4 wire, bedroom areas not required to be AFCI protected due to no new wiring being installed, check with Building inspector on ADA requirements for units that may be marketed as ADA. Panels may need lowered to comply. Temp wiring feeding sign not compliant, GFCI protection, installed by unlicensed person, shall repair with in 5 working days. Will schedule reinspect for temp wiring for Wed. 1-18-17.